Westinghouse CONTRACTOR SERIES 10KPRO Owner's Manual

Page of 106
32 
OPERATION
STOPPING THE GENERATOR
Normal Operation
During normal operation, use the following steps to stop 
your generator:
1.  Remove any connected loads from the control 
panel receptacles.
2.  Allow the generator to run at “no load” to reduce 
and stabilize engine and alternator temperatures.
3.  Turn the engine control switch to the OFF position.
4.  Turn the fuel shutoff valve to the OFF position.
During an Emergency
If there is an emergency and the generator must be 
stopped quickly, push the engine control switch to the 
OFF position immediately. 
STARTING THE GENERATOR 
USING REMOTE START
Before starting the generator, review 
Safety on page 7.
Before attempting to start the generator, verify the 
following:
x The engine is filled with engine oil (see Checking 
Engine Oil – 10KPRO on page 35 and Checking 
Engine Oil – 8KPRO on page 36).
x The generator is situated in a proper location (see 
Location Selection on page 24).
x The generator is on a dry surface (see Weather and 
Dry Surface on page 24).
x All loads are disconnected from the generator (see 
No Connected Loads on page 24).
x The generator is properly grounded (see Grounding 
the Generator on page 24).
x The ground fault sensor is working correctly (see 
Testing the Ground Fault Sensor on page 46).
!
 DANGER
Never use the generator in a location 
that is wet or damp. Never expose the 
generator to rain, snow, water spray or 
standing water while in use. Protect the 
generator from all hazardous weather 
conditions. Moisture or ice can cause a 
short circuit or other malfunction in the 
electrical circuit. 
!
 DANGER
Never operate the generator in an 
enclosed area. Engine exhaust 
contains carbon monoxide. Only 
operate the generator outside and away 
from windows, doors and vents.
NOTICE
The engine is equipped with a low oil shutdown 
switch. If the oil level becomes low, the engine will 
shut down and will not start until the oil is filled to the 
proper level.
Be sure the engine has the proper oil level before 
using. Failure to verify that the engine has the proper 
oil level could result in engine damage.
Disconnect all loads from the generator before 
starting. Failure to verify all loads are disconnected 
prior to starting the generator could result in damage 
to the connected appliances.
1.  Verify the battery is properly installed and both 
battery cables are attached (see Installing the 
Battery on page 16).
2.  Make sure the circuit breakers are properly set (see 
Figure 29 and Figure 30).
1
2
3
4
Figure 29 – Circuit Breakers – 10KPRO
1 -   120V Circuit 
Breaker
2 -   120V 30-Amp 
Circuit Breaker
3 -   240/120V  
30-Amp Circuit 
Breaker
4 -  Main Breaker