Hamilton Sundstrand Company Fuel Metering Valves XVG User Manual

Page of 36
 
 
 
Register 
Number 
XVG/eXVG Parameter 
Name 
Write 
Access 
Description Type 
Default 
Value 
7650 7651 
IDM_AO0CUROFF 
W4 
AO0 Current Offset:  range -4 to 4 counts 
Float 
7652 7653 
IDM_AO0VOLTGAIN 
W4 
AO0 Voltage Gain:  range 0.72 – 0.80 
Float 
7654 7655 
IDM_AO0VOLTOFF 
W4 
AO0 Voltage Offset:  range -4 to 4 counts 
Float 
7656 7657 
IDM_AO1CURGAIN 
W4 
AO1 Current Gain:  range 0.72 – 0.80 
Float 
7658 7659 
IDM_AO1CUROFF 
W4 
AO1 Current Offset:  range -4 to 4 counts 
Float 
7660 7661 
IDM_AO1VOLTGAIN 
W4 
AO1 Voltage Gain:  range 0.72 – 0.80 
Float 
7662 7663 
IDM_AO1VOLTOFF 
W4 
AO1 Voltage Offset:  range -4 to 4 counts 
Float 
7664 7665 
IDM_AO2CURGAIN 
W4 
AO2 Current Gain:  range 0.72 – 0.80 
Float 
7666 7667 
IDM_AO2CUROFF 
W4 
AO2 Current Offset:  range -4 to 4 counts 
Float 
7668 7669 
IDM_AO2VOLTGAIN 
W4 
AO2 Voltage Gain:  range 0.72 – 0.80 
Float 
7670 7671 
IDM_AO2VOLTOFF 
W4 
AO2 Voltage Offset:  range -4 to 4 counts 
Float 
7672 7673 
IDM_AI0VOLTGAIN 
W4 
AI0 Voltage Gain:  range 1.03 – 1.05 
Float 
7674 7675 
IDM_AI0VOLTOFF 
W4 
AI0 Voltage Offset:  range -(122.6 to 146.6) 
Float 
7676 7677 
IDM_AI1VOLTGAIN 
W4 
AI1 Voltage Gain:  range 1.03 – 1.05 
Float 
7678 7679 
IDM_AI1VOLTOFF 
W4 
AI1 Voltage Offset:  range -(122.6 to 146.6) 
Float 
7680 7681 
IDM_AI2VOLTGAIN 
W4 
AI2 Voltage Gain:  range 1.03 – 1.05 
Float 
7682 7683 
IDM_AI2VOLTOFF 
W4 
AI2 Voltage Offset:  range -(122.6 to 146.6) 
Float 
7684 7685 
IDM_AI3VOLTGAIN 
W4 
AI3 Voltage Gain:  range 1.03 – 1.05 
Float 
7686 7687 
IDM_AI3VOLTOFF 
W4
 
AI3 Voltage Offset:  range -(122.6 to 146.6) 
Float
 
7688 7689 
IDM_AI4VOLTGAIN 
W4
 
AI4 Voltage Gain:  range 1.03 – 1.05 
Float
 
7690 7691 
IDM_AI4VOLTOFF 
W4
 
AI4 Voltage Offset:  range -(122.6 to 146.6) 
Float
 
7692 7693 
IDM_AI5VOLTGAIN 
W4
 
AI5 Voltage Gain:  range 1.03 – 1.05 
Float
 
7694 7695 
IDM_AI5VOLTOFF 
W4
 
AI5 Voltage Offset:  range -(122.6 to 146.6) 
Float
 
7696 7697 
IDM_OVERPRESLIM 
W4
 
Overpressure Limit, range 200 to 600PSIA 
Float
 
450 
7698 7699 
IDM_MAXINTERR 
W4
 
Maximum integral position control 
contribution, units of velocity. Range 0.0 to 
1.999 
Float
 
0.0000
13 
7700 7701 
IDM_TR 
W4
 
Thermal aging reference temperature, units of 
deg C.  Range: 0.0 to 150.0 
Float
 
60.0 
7702 7703 
IDM_TITDB 
W4
 
Total inches traveled accumulator dead-band, 
units of inches. Range: 0.0 to 0.005 
Float
 
0.0005 
7704 7705 
IDM_INPRESCOEF2 
W4
 
Second order inlet pressure sensor correction 
coefficient. Range: -1.0 to 1.0 
Float
 
0.0 
7706 7707 
IDM_OUTPRESCOEF2 
W4
 
Second order inlet pressure sensor correction 
coefficient. Range: -1.0 to 1.0 
Float
 
0.0 
 
Table 16:  General Setup Parameters 
 
9.1.2  Position Interpolation Parameters 
 
The XVG/eXVG Fuel Metering Valve can be configured to operate with a non-linear 
stroke profile by adjusting the values in this table. The Position Interpolation Table is a 
43-point table, which maps a specific position to a linear demand position point. The first 
30 points in the table are spaced at 0.1mA intervals and the remaining points are spaced 
at 1.0mA intervals.  
 17