Perform the following steps to retrieve the fault records: 
 
1.  Read register 3045, IDM_RECORDS, to get the current number of fault 
records available in the XVG/eXVG.  The records are named 0, 1, 2, .. , n-1.  
Maximum  n = 16. 
2.  To retrieve first record, record 0, write 0 to register 3043, 
IDM_FRECORDNO. 
3.  Write 4 to register 3094, IDM_TESTCTRL. 
4.  Read registers 3028, 3029, 3044, 5026, 5028, 7050-7072 to complete record 
0. 
5.  Repeat steps 2, 3, 4, and 5, to retrieve record 1, 2, .., n-1. 
 
 
10.3  Change Gas Constant R and K Procedure 
 
Register 
Number 
XVG/eXVG Parameter Name 
Description 
Type 
Write 
Access 
3005 IDM_SETUPCONNECT 
Setup Mode: 1=Set Valve in Setup State, 2=Exit 
Setup and Reset CPU 
U16
 
W1 
3033 IDM_CALFLAGS 
Calibration 
Flags 
U16
 
W1 
3099 IDM_TESTSTR 
Test string, used for Modbus write access 
password. 
U16
 
W0 
7008 
IDM_MEASFLOW 
Measured Flow, PPH 
Float
 
Read
 
7518 IDM_CONSTR 
R Gas Constant: must be non-zero, default is 
Air, 53.34 
Float
 
W0 
7520 IDM_CONSTK 
K Gas Constant: must be non-zero, default is 
Air, 1.4 
Float
 
W0 
Table 25:  Parameters for Gas Constant R and K 
 
Perform the following steps to change gas constant R and K in real-time. 
 
1.  Read registers 7518, 7520, and 7008, to get the R, K, and corresponding 
measured flow values.  Take note of the R and K values for reference.  The 
only way to restore the default values without a valve close and reset (engine 
shutdown) is to write those values into the valve again. 
2.  Write registers 7518 and/or 7520 with appropriate new values. 
3.  Read register 7008 to get new measured flow value. 
4.  Read the registers that are of interest to your application. 
5.  If desired, save the new R and K value to the valve.  Note that the following 
SAVE or RESET procedure will CLOSE and RESET the valve. 
 
SAVE Parameters routine: 
 
-  Write a password to register 3099. 
-  Write 1 to register 3033.  Wait 100 milliseconds. 
-  Write 32 to register 3033.  Wait 100 milliseconds.   
-  Write 1 to register 3005.  Wait 100 milliseconds. 
 34