Tyco 4100U-S1 User Manual

Page of 138
 
 
F-4
 
 
The following lists the detectors approved for use with IDNet and shows current 
rating and numbers allowed per loop. 
 
Device Type 
Operating 
Current mA 
Maximum 
Number Allowed 
Per Loop 
Maximum 
Number 
Allowed Per 
Line 
4098-9714E 
Analogue Photoelectric 
Smoke Detector 
0.5  
(2 with LED 
on) 
250 40* 
4098-9717E 
Analogue Ionisation 
Smoke Detector 
0.5  
(2 with LED 
on) 
250 40* 
4098-9733E 
Analogue Heat Type A & 
B Detector 
0.5  
(2 with LED 
on) 
250 40* 
4098-9754E 
Analogue Multi 
(Heat/Photo) 
Detector 
0.5  
(2 with LED 
on) 
250 40* 
 
* Maximum allowed by AS1670.1. 
 
The 9714E, 9717E and 9733E detectors use a (4098-) 9789E addressable base 
or 9794E addressable sounder base, or 9793 addressable isolator base.  The 
9754E uses a 9796E addressable base or 9795E sounder base. 
 
The maximum specified loop/line resistance is 40
Ω. 
 
The maximum number of LEDs switched on during Alarm on an IDNet loop is 20. 
 
 
 
 
Compatible Detectors, IDNET