Tyco 4100U-S1 User Manual

Page of 138
 
 
6-5
 
 
Configuring the card consists of selecting the shield tie point, and setting the card address. 
 
If a shielded cable is used, connect the cable shield to the dedicated terminal on TB1 and 
use jumper port (P1) to select where the shield will be tied. 
 
•  Position 1 - 2 connects the shield to 0 V. 
•  Position 2 - 3 connects the shield to Earth. 
 
The card address is set on DIP switch SW1, which is a bank of eight switches (see figure 
below). From left to right, these switches are designated as SW1-1 through SW1-8. The 
function of these switches is as follows: 
 
•  SW1-1.  This switch sets the baud rate for the internal communications line 
running between the card and the CPU.  Set this switch to ON.   
 
•  SW1-2 through SW1-8.  These switches set the card’s address within the 
4100U-S1. Refer to the table in Appendix A for a complete list of the switch 
settings for all of the possible card addresses.  
 
Note:  You must set these switches to the value that was assigned to the card 
by the 4100U Programmer.  
 
 
 
 
 
 
 
 
1
 
8
 
7
 
6
 
5
 
4
 
3
 
2
 
 
Figure 6-3. DIP Switch SW1 
 
 
 
 
 
Configuring the Card 
Overview 
Setting the Shield 
Tie Point 
Setting the Address 
ON
OFF
Dip Switches SW1-2 through 
SW1-8 set the Card Address. 
Figure shows an Address of 3. 
4100 Comms Data Rate. 
Switch (SW1-1) 
Must Be Set to ON