Tyco 4100U-S1 User Manual
6-5
Configuring the card consists of selecting the shield tie point, and setting the card address.
If a shielded cable is used, connect the cable shield to the dedicated terminal on TB1 and
use jumper port (P1) to select where the shield will be tied.
use jumper port (P1) to select where the shield will be tied.
• Position 1 - 2 connects the shield to 0 V.
• Position 2 - 3 connects the shield to Earth.
• Position 2 - 3 connects the shield to Earth.
The card address is set on DIP switch SW1, which is a bank of eight switches (see figure
below). From left to right, these switches are designated as SW1-1 through SW1-8. The
function of these switches is as follows:
below). From left to right, these switches are designated as SW1-1 through SW1-8. The
function of these switches is as follows:
• SW1-1. This switch sets the baud rate for the internal communications line
running between the card and the CPU. Set this switch to ON.
• SW1-2 through SW1-8. These switches set the card’s address within the
4100U-S1. Refer to the table in Appendix A for a complete list of the switch
settings for all of the possible card addresses.
settings for all of the possible card addresses.
Note: You must set these switches to the value that was assigned to the card
by the 4100U Programmer.
1
8
7
6
5
4
3
2
Figure 6-3. DIP Switch SW1
Configuring the Card
Overview
Setting the Shield
Tie Point
Tie Point
Setting the Address
ON
OFF
Dip Switches SW1-2 through
SW1-8 set the Card Address.
Figure shows an Address of 3.
SW1-8 set the Card Address.
Figure shows an Address of 3.
4100 Comms Data Rate.
Switch (SW1-1)
Must Be Set to ON
Switch (SW1-1)
Must Be Set to ON