Patterson-Kelley MACH-05 User Manual

Page of 59
  MACH®  Series
 
Gas-Fired Boiler 
Installation 
 
 
Page  22 
Internal Setpoint: 
The internal setpoint is set with parameter 4. The 
boiler temperature control modulates the boiler to 
maintain this internal setpoint.  The upper and lower 
temperature differentials are used to instruct the boiler 
at what temperature to turn on and at what temperature 
to turn off. 
 
Item Parameter 
Value 
Allowable 
Range 
Setpoint 4 
160 
68-185 
Low Temp. Differential 
22 
10 
0-36 
High Temp. Differential 
23 
0-36 
Low Temp. Setpoint 
68 
59-140 
 
The boiler will modulate to try to maintain 160° F.  If 
the temperature increases above 169° F which is the 
setpoint 160° F + High Temp Differential 9°F the 
boiler will shut off.  Once it shuts off it will not restart 
until the temperature drops below 150° F which is the 
setpoint – Low Temp Differential.  The Low Temp Set 
Point will not permit the operator to adjust the setpoint 
below 68° F.  (See graph below.) 
 
Internal Setpoint
145
150
155
160
165
170
175
0
10
20
30
40
Time
Boiler Temperature
Boiler Set Point
Boiler Turns On
Boiler Turns Off
 
 
 
 
Domestic Priority: 
If an indirect domestic hot water (DHW) tank is 
connected, the DHW function of the boiler will 
activate when the DHW temperature controller 
(supplied by others) closes (Terminal 5 to 8 TB 1, 
refer to Section 6.1.1), indicating a call for heat from 
the DHW system.  The parameters should be set as 
follows: 
 
Item Parameter 
Value 
DHW Setpoint 
140 
DHW Setpoint Addition 
33 
30 
DHW Status 
DHW High Temp. Differential 
25 
DHW Low Temp. Differential 
24 
DHW Options 
35 
13 
 
 
In the above example, the boiler temperature will be 
set to the DHW Setpoint + the DHW Setpoint 
Addition (140ºF + 30ºF = 170ºF) when the DHW 
temperature controller indicates a call for heat from 
the DHW system.  When the DHW system calls for 
heat, the Central heat pump output (Terminal 10 
TB2) de-energizes and the DHW pump output 
(Terminal 11 TB2) energizes providing 120 VAC 
power is provided to energize a relay coil for the 
DHW pump.  The DHW status should be set to 1 
(DHW system ON).