Patterson-Kelley MACH-05 User Manual

Page of 59
  MACH®  Series
 
Gas-Fired Boiler 
Parts and Technical Support 
 
 
Page  37 
6.1
  
W
IRING 
D
IAGRAMS
 
 
6.1.1 Terminal Block Assignments – High Voltage Circuit (TB2) 
 
Terminal Number 
Label 
Description 
 
 
 
115 VAC LINE 
115 VAC NEUTRAL 
Boiler Supply Power, 115 VAC, 60 HZ, 1 ph, 8 amp 
115 VAC NEUTRAL 
Aux. Switched Output 
115 VAC NEUTRAL 
Boiler Circ. Pump 
115 VAC NEUTRAL 
DHW Circ. Pump 
6 GROUND 
Boiler 
Supply 
Ground 
7 GROUND 
8 GROUND 
Aux .Ground 
115 VAC SW. OUTPUT 
Aux. Switched Output, Pilot duty only, 1 amp max. 
10 
115 VAC CIRC. PMP 
CONTACTOR 
Boiler Circ. Pump, Pilot duty only, 1 amp max. 
 
 
 
11 
115 VAC DHW PMP 
CONTACTOR 
DHW Circ. Pump, Pilot Duty only, 1 amp max. 
12 
MASTER ALARM RELAY 
13 
MASTER ALARM RELAY 
Dry Contacts, 24 VAC max, 1 amp max. 
14 
THREE WAY VALVE RELAY 
15 
THREE WAY VALVE RELAY 
DHW Dry Contacts, 24 VAC max, 1 amp max. 
16 DAMPER 
RELAY 
17 DAMPER 
RELAY 
Combustion Air Damper, Dry Contacts, 24 VAC max, 1 amp 
max.