ƒ  5.4.5.c  
Automatic Reset 
The TE Series starter provides for automatic reset on certain non-
critical faults and Over Load.  For non-critical fault resets, see 
section 5.6.9 for program details of F052 and F053. For automatic 
Over Load reset, see section 3.1 and 5.6.1 for programming details. 
 
ƒ  5.4.5.d 
 Lockout Functions 
Lockout functions such as Minimum Time Between Starts and 
Starts per Hour are not true fault conditions. They are based on the 
internal Real Time Clock (RTC). When control power is removed, 
the RTC value is quickly stored. Upon return of power, the timer 
values are updated from the RTC for elapsed time. If the Lockout 
Time has not expired, the TE Series cannot be started. To reset the 
Lockout Times for emergency restart, see section 5.6.12, under 
F071. 
 
ƒ  5.4.5.e 
Changing to Default Screen During Fault 
In some cases it may be necessary to alter programmed 
parameters in order to test or make changes to clear a fault (such 
as Phase Loss) or to view the more detailed fault history in F085 – 
F097. To accomplish this, you must get to the Status Screen so the 
Fn button becomes active. When in a Fault Screen, pressing the 
Right or Left Arrow buttons will take you to the Status Screen. From 
there, you can hit the [Fn] key to enter the Programming Mode and 
move to different functions.