Section 1.0 - Installation 
 
When installed and operated as described in these instructions, the Osburn Model 2200 Bay Wood Stove is 
suitable for use as a freestanding wood stove in either residential or mobile home installations. 
The Model 2200 is not intended for installation in a bedroom. 
In Canada the CSA B365 Installation Code for Solid Fuel Burning Appliances and Equipment and the CSA 
C22.1 Canadian National Electrical Code are to be followed in the absence of local code requirements.  In 
the USA the ANSI NFPA 70 National Electrical Code and NFPA 211 Standard for Chimneys, Fireplaces, 
Vents and Solid Fuel-Burning Appliances are to be followed in the absence of local code requirements. 
In addition to the national installation codes, local building and/or fire officials (or other authorities having 
jurisdiction) should be contacted to determine what restrictions and installation requirements might locally 
apply. 
 
1.1 General 
Installation
 
 
1.  Proper ventilation is required.   
2.  Do not connect this unit to any air distribution duct. 
3.  Connect the stove only to a lined masonry chimney conforming to national and local building 
codes for use with solid fuel, or to a listed factory built chimney suitable for use with solid fuel.  
 
Clearances To Combustibles 
 
1.2.1  Canada and the U.S.A.
 
 
Clearances to any combustibles when measured directly out from the front and up from the top of 
The stove must be a minimum of 48" (1219 mm).  The stove must also be placed so as to maintain 
the minimum clearances to combustible walls specified for the connector used. (See Table 1.1 and 
Figure 1.1). 
 
 
Canada & USA using 
Single Walled Connector 
 
Canada & USA using 
Horizontal Single Walled 
Connector 
Canada & USA Mobile 
Home & reduced clearance 
installations using listed 
Double Walled Connector 
To Unit:
 
 
 
 
Sidewall  
A
 
17" (432 mm)
 
19" (483 mm)
 
20.5"  (521 mm)
 
Back wall 
B
 
13.5" (343 mm)
 
13.5" (343 mm)
 
6.0" (152 mm)
 
Corner 
10" (254 mm)
 
10" (254 mm)
 
3.0" (76 mm)
 
To Connector:
 
 
 
 
Sidewall D
 
27" (686 mm)
 
29" (737 mm)
 
30" (762 mm)
 
Backwall E
 
16" (406 mm)
 
16" (406 mm)
 
7.25" (184 mm)
 
Corner F
 
20" (508 mm)
 
20" (508 mm)
 
13" (330 mm)
 
Table 1.1
 Minimum
 Clearances to Combustible Materials – Canada and the U.S.A.