John Deere Products & Services Portable Generator DCA70SSJU4i User Manual

Page of 120
dca70SSJU4i 60 hz generator• operation manual — rev. #2 (04/09/14) — page 17
iNstaLLatiON
outdoor installation
Install the generator in a area that is free of debris, 
bystanders, and overhead obstructions. Make sure the 
generator is on secure level ground so that it cannot slide 
or shift around. Also install the generator in a manner so 
that the exhaust will not be discharged in the direction of 
nearby homes.
The installation site must be relatively free from moisture 
and dust. All electrical equipment should be protected from 
excessive moisture. Failure to do will result in deterioration 
of the insulation and will result in short circuits and 
grounding.
Foreign materials such as dust, sand, lint and abrasive 
materials have a tendency to cause excessive wear to 
engine and alternator parts.
indoor installation
Exhaust gases from diesel engines are extremely 
poisonous. Whenever an engine is installed indoors the 
exhaust fumes must be vented to the outside. The engine 
should be installed at least two feet from any outside wall. 
Using an exhaust pipe which is too long or too small can 
cause excessive back pressure which will cause the engine 
to heat excessively and possibly burn the valves.
mounting
The generator must be mounted on a solid foundation (such 
as concrete) and set firmly on the foundation to isolate 
vibration of the generator when it is running. The generator 
must set at least 6 inches above the floor or grade level (in 
accordance to NFPA 110, Chapter 5-4.1). 
dO NOT remove 
the metal skids on the bottom of the generator. They are 
to resist damage to the bottom of the generator and to 
maintain alignment.
  caution
Pay close attention to ventilation when operating the 
generator inside tunnels and caves. The engine exhaust 
contains noxious elements. Engine exhaust must be 
routed to a ventilated area.
generator grounding
To guard against electrical shock and possible damage to 
the equipment, it is important to provide a good 
eaRTH 
ground (Figure 3).
Article 250 (Grounding) of the National Electrical Code 
(NEC) provides guide lines for proper grounding and 
specifies that the cable ground shall be connected to the 
grounding system of the building as close to the point of 
cable entry as practical.
NEC articles 250-64(b) and 250-66 set the following 
grounding requirements:
1.  Use one of the following wire types to connect the 
generator to earth ground.
a.  Copper - 8 AWG (5.3 mm
2
)
b.  Aluminum - 6 AWG (8.4 mm
2
)
2.  When grounding the generator (Figure 2) connect the 
ground cable between the lock washer and the nut on 
the generator and tighten the nut fully. Connect the 
other end of the ground cable to earth ground. 
3.  NEC article 250-52(c) specifies that the earth ground rod 
should be buried a minimum of 8 ft. into the ground.
NOTICE
When connecting the generator to any buildings 
electrical system 
alWaYs consult with a licensed 
electrician.
NOTICE
This generator has a permanent bonding conductor 
between the generator stator windings and the frame.