John Deere Products & Services Portable Generator DCA70SSJU4i User Manual

Page of 120
dca70SSJU4i 60 hz generator• operation manual — rev. #2 (04/09/14) — page 31
3Ø-600v auto-transformer
3Ø, 600 VAC can be achieved via the auto-transformer 
module. This module provides the necessary electronics 
to convert the 3Ø, 480 VAC inut voltage to a 3Ø, 600 VAC 
output voltage.
The 3Ø, 600 VAC ouput voltage cannot be achieved unless 
the voltage selector switch (Figure 29) is placed in the 3Ø, 
480/277 position.
Figure 29. Voltage Selector Switch 
3Ø-240/139V Position (600 VAC Auto-Transformer)
3Ø-600vac load connections
1.  Loosen the latches on the control box enclosure and 
open the door.
2.  Drill a 1-1/2 inch hole at the bootom control box 
enclosure as shown in Figure 30.
Figure 30. Control Box Enclosure (Drilling)
  daNgeR
When connecting the load wires make sure the 
generator is 
oFF. The possibility of electrocution exists 
causing severe bodily harm even death!
CIRCUIT BREAKER
ENCLOSURE
DRILL
NEW HOLE
(1-1/2” DIA.)
STRAIGHT
FITTING
LOCK
RING
BUSHING
3.  After drilling, make sure all shavings and debris have 
been removed from the enclosure.
4.  Install customer supplied conduit, fittings and bushing 
through enclosure hole opening. 
5.  Next, route the customer supplied 5 wires through the 
straight conduit fitting.
6.  Connect the 3 load wires (
RedBlacK and Blue
to the load side (bottom) of the circuit breaker,
 t1T2 
and 
t3 respectively. Reference Figure 31
Figure 31. Control Box Enclosure  
Load Connections
7.  Connect the neutral wire (
White) to the neutral bus 
bar.
8.  Connect the ground wire (
gReeN) to the ground 
terminal. 
9.  Torque all wires to 45 lbf-in (5 N.m).
10.  Once all wires have been securely tighten, close  
control box enclosure door and securely tighten the 
control box door latches.
L1
T1 T2 T3
L2 L3
70 AMP
CIRCUIT BREAKER
LOAD
WIRES
FROM
600 VAC
AUTO
TRANSFORMER
NEUTRAL BUS BAR
GROUND
TERMINAL
600 VaC CONNeCtiONs