Moeller Marine XI/OC SIGNAL MODULES 05/02 AWB2725-1452GB User Manual

Page of 38
05/02 AWB2725-1452GB
Wiring up the analogue 
module
13
Wiring up the analogue module
X
Short-circuit any unused channels on the analogue input 
module.
X
Short-circuit any unused current outputs on the analogue 
output module (2 to 3 channels).
X
Only use shielded cables for connection to external equipment. 
X
Route the cables separately from power leads or signal cables 
that carry differential voltages.
X
Depending on the prevailing electromagnetic environment, one 
or both ends of the shielding should be grounded.
X
Lay the AC supply power cables in separate ducts to those used 
for signal or data cables.
X
Lay signal and data cables as close as possible to the grounded 
surfaces of the switchgear cabinet.
Project planning
Details on project planning can be found in the following manuals
XC-CPU400/600: AWB2700-1428
XC-CPU100/200: AWB2724-1453
Dimensions
Signal modules
Module rack
Figure 14:
Dimensions of the signal modules
95
30
100
21
Figure 15:
Dimensions of the module racks XIOC-BP-XC, XIOC-BP-2
Figure 16:
Dimensions of the module rack XIOC-BP-XC1, XIOC-BP-3
53.5
53.5
50
50
1
3.5
3
60
39
16
3.5
3
90
39
53.5
53.5
50
50
1
16
60