Lucent Technologies Uninterruptible Power Systems 3000 VA User Manual

Page of 75
     
#" !     " ! #  $ $   !!# 

   
The

Indicator and the
Indicator illuminate simultaneously, indicating
Bypass Mode (see Figure 16). When the UPS is in Bypass Mode, the load is powered
by utility power. However, utility power continues to be passively filtered by
the UPS.
LOAD ON
UNIT ON
BYPASS
OVERLOAD
1
2
3
OUTPUT ON
        
   
When the UPS is operating during a power outage, the alarm beeps several times
initially, and then once every 10 seconds while in Battery Mode. The
Indicator
illuminates. The front panel displays the approximate percentage of battery capacity
remaining (see Figure 17). When the utility power returns, the UPS switches to
Normal Mode operation while the battery recharges.
BATTERY
ONLINE
>75%
CAPACITY
REMAINS
BATTERY
ONLINE
>50%
CAPACITY
REMAINS
BATTERY
ONLINE
>25%
CAPACITY
REMAINS
BATTERY
ONLINE
BATTERY
ONLINE
SHUTDOWN
IMMINENT
LOW
BATTERY
WARNING
OVERLOAD
1
2
3
OUTPUT ON
        
If battery capacity becomes low while in Battery Mode, the I3 Indicator begins to
flash and the Output On Indicator remains lit, indicating approximately two
minutes before UPS shutdown. The alarm beeps every two seconds.
When shutdown is imminent, the Output On Indicator flashes. These warnings are
approximate, and the actual time to shutdown may vary significantly. Once these
warnings are indicated, immediately complete and save your work to prevent data
loss and similar difficulties. When utility power is restored after the UPS shuts
down, the UPS automatically connects to the load when the startup is complete.