Configuration, Startup, and Operation 
 
 
of Recorder with Display 
12/03 
DR4300 Circular Chart Recorder Product Manual 
91 
4.3.10  Totalizer Parameters Set Up Group 
Introduction 
If the recorder hardware supports totalizer functions, the functions in this group are used to calculate and 
display the total flow volume as measured by the input. The displayed value is six digits with a 
configurable scale factor.  
The totalized value can be in engineering units different from the input, by setting INP EU (engineering 
units of input) and TOT EU (engineering units of totalized value). 
The total can be displayed with one or two decimal places to provide more resolution for selections that 
produce smal values (e.g., Acre-Feet). A Scaler configuration other than one will override the decimal 
display. 
Control group prompts 
Table 4-8 lists all the function prompts in the totalizer function group.  
For a 2-pen recorder, the desired input channel is displayed on the left side of the operator interface. Press 
FUNC  to select channel. 
Press SETUP  key until “TOTAL” appears in the lower display. 
Press FUNC  key to select the parameters. 
Table 4-8  Totalizer Function Definitions 
Lower Display 
Prompt 
Upper Display  
Range of Setting  
or Selection 
Parameter  
Definition 
(actual current 
totalized value) 
 
 
(current scale factor) 
Example: E1 
VIEW CURRENT TOTALIZED VALUE
—This selection lets 
you view the current totalized value. 
In the example shown, E1 represents the exponential value 
that applies to the total (total times 10
1
).  
See “SCALER” function prompt in this group for choices. 
RESET 
YES  
NO  [factory setting] 
 
RESET TOTALIZER TO ZERO
—This parameter is used to 
reset the totalizer to zero. 
Selecting YES will reset the totalizer to zero. When the reset 
action has been performed, the parameter will be set to NO 
automatically. 
ATTENTION
 In order for this prompt to appear, the 
“RSTABL” function (described later in this table) must be set 
to “KEY”. 
TOTAL  
ENAB 
DIS  [factory setting] 
TOTALIZATION FOR INPUT
—This parameter is used to 
enable or disable the totalizer function. This prompt appears 
first if “DIS” is the current choice. 
ENABLE allows configuration of the rest of the prompts 
associated with totalization.