4.3.11  Control Parameters Set Up Group 
Introduction 
If the recorder hardware supports outputs, the functions in this group are used to configure how the 
recorder will control the process. (If configuring a limit controller, see Subsection 4.3.22 for special limit 
control configuration parameters.) 
Control group prompts 
Table 4-9 lists all the function prompts in the control set up group. For a 2-pen recorder, the desired input 
channel is displayed on the left side of the operator interface. Press  FUNC  to select channel. Press 
SETUP  key until “CONTRL” appears in the lower display.  Press  FUNC  key to select the parameters. 
Table 4-9  Control Parameter Definitions 
Lower Display 
Prompt 
Upper Display  
Range of Setting  
or Selection 
Parameter  
Definition 
CONTRL 
ENAB 
DIS         [factory setting] 
Enables control. 
Disables control. If control is disabled here, the rest of the 
functions in this group will not be displayed. All alarm 
group functions will be displayed. 
NumSPs 
ONE  [factory setting] 
TWO 
NUMBER OF SETPOINTS
—If this is set to TWO, then 
the operator will be able to select the setpoint using the 
UseSPn operating parameter prompt. 
OUTALG 
 
OUTPUT ALGORITHM 
—Use to specify the type of 
output.  
 
RLY        [factory setting] 
RELAY SIMPLEX
—Type of output using one SPDT 
relay. Its contacts can be wired for normally open (NO) or 
normally closed (NC) action. 
 
Control group function “HYST” is affected. 
The second relay is available for alarming, and alarm 
group functions will be displayed for Alarm 2. 
 
RLYD 
RELAY DUPLEX
—Type of output using two SPDT 
relays. Its contacts can be wired for normally open (NO) 
or normally closed (NC) action. 
Control group function "DBAND" is affected. 
No relay is available for alarming, and no alarm group 
functions will be displayed. 
 
CUR 
CURRENT SIMPLEX
—Type of output using one 4 mA to 
20 mA signal that can be fed to a positive or negative 
grounded load of 0 to 600 ohms. The current output 
signal can be recalibrated as described in Section 5 to 
use any range within 4 mA to 20 mA to represent 0 to 100 
% output.  
 
CurT 
CURRENT/TIME DUPLEX (Relay = Heat)
—Variation of 
duplex with current active for 0 % to 50 % output (tuning 
set 2) and relay active 50 % to 100 % output (tuning set 
1). 
Control group functions “CURRNG” and "DBAND" are 
affected.