Honeywell Work Light DR4300 User Manual

Page of 262
DR4300 Circular Chart Recorder 
106 
DR4300 Circular Chart Recorder Product Manual 
12/03 
4.3.15  Alarms Set Up Group 
Introduction 
If the recorder hardware supports outputs, one or both relays can be used for alarming. An alarm is an 
indication that an event that you have selected during configuration (process variable, for example) has 
exceeded one or more alarm limits. There are two alarms available for each pen (assuming no relay is 
being used for control). Each alarm has two setpoints. There are two alarm output selections, high and low. 
You can configure each setpoint to alarm either high or low. Each alarm has an adjustable hysteresis of 0.0 
% to 100.0 % that is configurable for that alarm's setpoint.  
If the “OUTALG” function in the control group is set to “RLYD”, both relays on the printed circuit 
assembly for the pen being configured are used for control, and the prompts in the alarm group will not be 
displayed. If “OUTALG” is “RLY”, or if the recorder is a limit controller, then Relay 1 is used for control. 
In these cases only the prompts for the second alarm (Relay 2) will be displayed.  
If “TIMER” is set to “ENAB”, then Relay 2 is used by the timer and prompts for the second alarm will not 
be displayed. 
Alarms group prompts 
Table 4-13 lists all the function prompts in the alarms set up group and their definitions.   
For a 2-pen recorder, the desired input channel is displayed on the left side of the operator interface.  
Press FUNC  to select channel. 
Press SETUP  key until “ALARMS” appears in the lower display. 
Press FUNC  key to select the parameters. 
Table 4-13  Alarm Parameter Definitions 
Lower Display 
Prompt 
Upper Display  
Range of Setting  
or Selection 
Parameter  
Definition 
A1S1TY* 
 
 
NONE   [factory setting] 
INP 
DEV 
ALARM 1 SETPOINT 1 TYPE
—Select what you want 
Setpoint 1 of Alarm 1 to represent. 
NO ALARM 
INPUT PV 
DEVIATION
 of input from setpoint 
A1S2TY* 
Same as A1S1TY 
ALARM 1 SETPOINT 2 TYPE
—Select what you want 
Setpoint 2 of Alarm 1 to represent. The selections are the 
same as A1S1TY. 
*For Deviation Alarm to function: control must be enabled. If On/Off control is selected, only alarm #2 is available for Deviation. 
A1S1VA
 
–999 to 9999 
 
[factory setting = 100]
 
ALARM 1 SETPOINT 1 VALUE
—This is the value at 
which you want the alarm type chosen in prompt 
"A1S1TY" to actuate. The appropriate value depends on 
what the setpoint has been configured to represent. 
A1S2VA 
–999 to 9999 
 
[factory setting = 100]
 
ALARM 1 SETPOINT 2 VALUE
—This is the value at 
which you want the alarm type chosen in prompt 
"A1S2TY" to actuate. The appropriate value depends on 
what the setpoint has been configured to represent.