DR4300 Circular Chart Recorder Product Manual 
12/03 
C.4  Setpoint Program Prompt Hierarchy 
Table C-1 lists all the function prompts for Setpoint Program data configuration in the order of their 
appearance.  These prompts are available when SPPROG is enabled in the SPRAMP set up group 
described in Section 4. 
All parameters may be changed while the program is disabled or in HOLD. 
 
Table C-1  Prompt Hierarchy and Available Selections 
Lower Display 
Prompt 
Upper Display  
Range of Setting  
or Selection 
Parameter  
Definition 
SPPROG 
 
 
 
 
 
 
DIS 
ENAB 
SETPOINT PROGRAMMING—This must be set to ENAB 
for the setpoint program feature to work, and for the 
associated operating parameters to be displayed. 
SPRAMP must be disabled.  (See Section 4.) 
DIS—Disabled  
ENAB—Enabled 
START 1 
1,3,5,7,9,11,13,15,17,19, 
21,23 [factory setting=1] 
START SEGMENT FOR PROGRAM 1—Enter the 
number of the first segment in Program 1. 
END 1 
2,4,6,8,10,12,14,16,18,20,22,
24 [factory setting=6] 
END SEGMENT FOR PROGRAM 1—Enter the number 
of the last segment in Program 1. 
START 2 
1,3,5,7,9,11,13,15,17,19, 
21,23 [factory setting=7] 
START SEGMENT FOR PROGRAM 2—Enter the 
number of the first segment in Program 2. 
END 2 
2,4,6,8,10,12,14,16,18,20,22,
24 [factory setting=12] 
END SEGMENT FOR PROGRAM 2—Enter the number 
of the last segment in Program 2. 
START 3 
1,3,5,7,9,11,13,15,17,19, 
21,23 [factory setting=13] 
START SEGMENT FOR PROGRAM 3—Enter the 
number of the first segment in Program 3. 
END 3 
2,4,6,8,10,12,14,16,18,20,22,
24 [factory setting=18] 
END SEGMENT FOR PROGRAM 3—Enter the number 
of the last segment in Program 3. 
START 4 
1,3,5,7,9,11,13,15,17,19, 
21,23 [factory setting=19] 
START SEGMENT FOR PROGRAM 4—Enter the 
number of the first segment in Program 4. 
END 4 
2,4,6,8,10,12,14,16,18,20,22,
24 [factory setting=24] 
END SEGMENT FOR PROGRAM 4—Enter the number 
of the last segment in Program 4. 
RECYCL 
0 to 99 
[factory setting=0] 
RECYCLES—Enter the number of times the program 
selected for execution will be repeated. 
SOKDEV 
–99.9 to 99.9 engineering 
units 
 
[factory setting=0.00] 
SOAK DEVIATION—Enter the acceptable deviation from 
setpoint during a soak cycle.  If the PV differs from the 
setpoint by more than the value of SOKDEV, soak time is 
frozen.   
There are no guaranteed soaks if SOKDEV = 0.