Start-up Checklist
Date of Start-up
Location
CONDENSING UNIT
MODEL #
ELECTRICAL
•  Check Compressor Amps for COOLER and
  FREEZER compressors. Should match
  nameplate.
   
YES 
NO
PIPING
•  Is suction line trapped at the Cooler?
   
YES 
NO
•  Is suction line trapped at the Freezer?
   
YES 
NO
DRAIN LINES
•  Are drain lines sloped properly?
   
YES 
NO
•  Is drain line trapped outside the Cooler?
   
YES 
NO
•  Is drain line trapped outside the Freezer?
   
YES 
NO
•  Is heat tape wrapped along entire length of
  the drain line in the Freezer?
   
YES 
NO
•  Is heat tape plugged in and heating the drain
  line?
   
YES 
NO
INSULATION
•  Are Liquid lines fully insulated?
   
YES 
NO
•  Are Suction lines fully insulated?
   
YES 
NO
SYSTEM CHECKS
•  Check Compressor Superheat for the
  COOLER (Should be between 20°F. & 30°F.)
   
YES 
NO
•  Check Compressor Superheat for the
  FREEZER (Should be between 20°F. & 30°F.)
   
YES 
NO
•Force unit into a Defrost Check heater amps.
  Should match nameplate amps.
   
YES 
NO
•  Check LPS Time Delay Relays. Should be
  set at 1 minute for both the COOLER and
  FREEZER.
   
YES 
NO
•  Check Low Pressure Switch on FREEZER. Should be set 
at 0 psig Cut-out/10 psig Cut-in.
   
YES 
NO
•  Did FREEZER and COOLER cycle off on LPS at Set-point 
Temperature?
   
YES 
NO
•  Is the sight glass free of bubbles?
   
YES 
NO
•  Are the COOLER and FREEZER fans at proper speeds?
   
YES 
NO
•  Check system for refrigerant leaks. Are there any 
leaks on the COOLER, FREEZER, CONDENSING UNIT or 
INTERCONNECTING PIPING?
   
YES 
NO
•  Check system piping for unusual vibration or noise. Is 
there any unusual vibration or noise on the COOLER, 
FREEZER, CONDENSING UNIT or INTERCONNECTING 
PIPING?
   
YES 
NO