1.4  Electrical Connections 
The HFG2.0 is suitable for use in hazardous locations. See the General 
Specification Summary in Section 1.2 for certifications. Ensure compliance 
with the factory recommendations, and that wiring is in accordance with 
local requirements. 
WARNING: 
94/9/EC (ATEX) Compliance – Special Conditions for Safe Use:   
Two special factory-sealed unions are mounted on the equipment to 
ensure the electrical connection to the network and to provide the 
feedback signal to the user.  
The installation of these devices and the final connections to the 
conduit shall comply with the requirements of the European 
standards.  
Ground Connection 
The case of the HFG2.0 features a threaded hole (0.250-20 UNC-2B 
female thread) that is dedicated for the ground connection. This hole has 
been left unpainted and uncoated to ensure a good electrical contact. 
This threaded hole is located on the clevis end of the unit, (see 
Figure 1-6, Figure 1-7 or Figure 1-8). Use a screw with a 0.250-20 UNC-
2A thread to connect the case of the HFG2.0 to the same ground plane 
as the user’s controller. 
 
Power Connections 
The HFG2.0 operates on a 120VDC (nominal), user-provided input 
voltage, which is supplied to the unit through the integral four-wire power 
harness. See Table 1-1 for the wire list for the HFG2.0 power harness. 
See Figure 1-9 for the HFG2.0 system power wiring diagram. See Figure 
1-10 for a typical power connection with a power supply. See Figure 1-11 
for a typical power connection with a battery. 
 
WIRE COLOR 
FUNCTION 
AWG 
RED Power 
14 
WHITE/RED Power 
(AUX) 
14 
GREEN Power 
Return 
14 
WHITE/GREEN 
Power Return (AUX) 
14 
Table 1-1.  Wire List for HFG2.0 Power Harness