Hamilton Sundstrand Company Gas Fuel Metering Valve HFG2.0 User Manual

Page of 70
 
 
 
PARAMETER 
DESCRIPTION 
FACTORY 
SETTING 
Part Number 
Describes part number of actuator model 
Per Drawing 
Actuator Type 
Describes type of actuator 
Stand Alone 
Command Source 
Sets type of command signal  
Analog 
Home Controls 
the 
direction the actuator will 
move, extending or retracting, to find the 
mechanical stop (HOME) 
Extend 
Span 
Sets the maximum stroke length, 
measured from the HOME position 
1.0 inches 
 
Stop Position 
Sets the signal loss position, measured 
from the HOME position 
0.0 inches 
Interpolation Table  
Sets how Demand signal is interpolated 
between defined points 
Linear 
Position Loop Constant 
 
63 
Current Loop PID Constants 
 
 
Proportional 
 
2.0 
Integral 
 
200 
Derivative 
 
Velocity Loop PID Constants 
 
 
Proportional 
 
30 
Integral 
 
3,000 
Derivative 
 
Maximum Velocity  
Sets the maximum velocity 
10 in/s 
Maximum Force 
Sets the maximum force output 
1267 lbf 
Maximum Homing Velocity 
Sets the maximum velocity used to find 
the HOME position 
0.5 in/s 
Maximum Homing Force 
Sets the maximum force the HFG2.0 will 
use to find the HOME position 
500 lbf 
Maximum Holding Force 
Sets the maximum force to be used to 
hold at the HOME position while the 
position demand is < 4.1mA and > 2mA 
500 lbf 
Table 3-5.  Typical HFG2.0 Setup Parameters With Default Values 
 
 
CH. 3: OPERATING THE HFG2.0 
51