Hamilton Sundstrand Company Gas Fuel Metering Valve HFG2.0 User Manual

Page of 70
 
 
Symptom 
Probable Causes 
Corrective Action 
RS232 Interface Inoperative  Incorrect wiring 
 
 
 
No or low 120 VDC power  
COM1 not connected 
RESET or RUN command is 
ON 
Ensure WHITE/ORANGE/YELLOW, 
WHITE/ORANGE/BLUE, WHITE/ORANGE/GREEN 
wires correctly connected to valve and laptop PC. 
 
Ensure 120 VDC Primary System Power at Valve 
Check laptop/PC com port 
Remove RESET or RUN command 
Table 5-1.  Initial Installation Troubleshooting Chart 
Symptom 
Probable Causes 
Corrective Action 
No valve feedback 
No or low 120 VDC  power 
Self-protective valve auto shut 
down 
Ensure 120 VDC at valve 
Upload Fault File- check for motor windings over -
temperature faults. 
Check for valve contamination 
FAULT alarm 
Various 
Upload Fault File to identify source of fault 
Clear indicated fault 
OVER TEMP alarm 
Ambient temperature limit 
exceeded 
 
Electronics or motor winding 
temperature out of range 
Allow actuator to cool and re-start 
Reduce ambient temperature 
Check for valve contamination 
FAULT and OVERTEMP 
alarm 
No 120 VDC Power 
DSP Failure 
Ensure 120 VDC at actuator 
Contact factory 
 
Table 5-2.  HFG2.0 In-Service Troubleshooting Chart 
For troubleshooting purposes, use Table 5-3 to verify the valve electrical 
continuity integrity. 
Disconnect the HFG2.0 power and digital harness connectors and use a 
digital multi-meter (DMM) to check the resistance values between the 
wires indicated on the table. If an open circuit is detected, send the 
HFG2.0 to Precision Engine Controls Corporation for test and repair. 
WARNING – Shock Hazard 
Remove all power to the HFG2.0 prior to continuity check. 
 
CH. 4: TROUBLESHOOTING THE HFG2.0
 
57