Gentex The Gentex Model ST/HS strobe and horn/strobe ST/HS User Manual
(PANEL VOLTAGE-APPLIANCE MIN. VOLT) X WIRE CONDUCTIVITY
TOTAL CURRENT DRAW
}
{
MAX. WIRE
DISTANCE =
(IN FEET)
DISTANCE =
(IN FEET)
WIRE
CONDUCTIVITY
18AWG
60
16AWG
95
14AWG
153
12AWG
244
Includes wire to and from appliance.
CAUTION: Applies only to regulated
supplies. Assumes all appliances are at the end of wire run (worst case).
HORN RATINGS
HORN
VOLTAGE
dBA @
10Ft. Per
UL464
dBA @
10Ft.
Anechoic
DC(mA)
FWR(mA)
16VDC
76-88
90
19
-
24VDC
76-88
92
26
-
33VDC
76-88
95
34
-
16VFWR
76-88
90
-
35
24VFWR
76-88
92
-
43
33VFWR
76-88
95
-
49
STROBE CURRENT RATING
DC (mA)
FWR (mA)
Candela
Voltage
Inrush
Peak
Operating Inrush
Peak
Operating
16
162
118
63
174
189
79
15
24
178
145
42
182
181
61
33
178
172
34
182
189
57
16
212
140
99
240
188
119
30 & 15/75
24
248
144
66
256
187
84
33
256
179
52
260
192
72
16
310
198
134
310
286
169
60
24
314
218
84
322
291
110
33
322
274
61
330
295
86
16
320
216
161
312
307
209
75
24
316
243
100
324
285
139
33
336
289
75
328
267
108
16
396
228
193
392
292
247
110
24
396
247
118
392
304
160
33
400
286
86
408
308
123
V. CHECKOUT AND TROUBLESHOOTING
1. Supply power to the system control panel. The auxiliary signaling appliances in the system should not be activated.
2. If the signal is activated:
2. If the signal is activated:
· Check all smoke and fire detectors in the system to make sure they have not been activated.
· Check all wiring connections to make sure the signal detection circuits are not reversed or shorted together. Check wire color codes and traces.
· Verify that the jumpers are properly set on both the control module and signal appliance. If the jumper on the AVS44 is as shown in Fig. 3, the
· Check all wiring connections to make sure the signal detection circuits are not reversed or shorted together. Check wire color codes and traces.
· Verify that the jumpers are properly set on both the control module and signal appliance. If the jumper on the AVS44 is as shown in Fig. 3, the
horns will not produce any sound unless there is an input to the H+ and H- terminals on the control module.
3. To test the signal appliances, trip the auxiliary panel or activate the alarm circuit at the main control panel or activate one of the fire detection units in
the system. All auxiliary signals should be activated.
4. An operational test on this product should be conducted in accordance with National Standards or at a minimum annually and more often if dictated
by local and state codes or authorities having jurisdiction.
Pg. 3
Note: Units have been tested to O
O
C, 49
O
C and 93% humidity and are rated 20-30vdc/vFWR -20%, +10%, per
CAN/ULC S526-M87. The 15/75 model is rated 15cd per UL 1971 and CAN/ULC S526-M87. Units are rated
16-33vdc/vFWR absolute per UL464 and UL1971.
16-33vdc/vFWR absolute per UL464 and UL1971.