Some non-volatile memory faults are user-addressable. Use a HART 
Communicator to diagnose the error and determine if it is repairable. Any 
error message that ends in “FACTORY” is not repairable. In cases of non 
user-addressable errors, you must replace the transmitter. Contact 
Rosemount Nuclear Instruments Inc. at (952) 949-5210 if you need 
assistance.
FAIL ELECT
The transmitter electronics board is malfunctioning due to an internal fault. 
Some of the FAIL ELECT errors are user-addressable. Use a HART 
Communicator to diagnose the error and determine if it is repairable. Any 
error message that ends in “FACTORY” is not repairable. In cases of non 
user-repairable errors, you must replace the transmitter. Contact Rosemount 
Nuclear Instruments, Inc. at (952) 949-5210 if you need assistance.
FAIL CONFIG
A memory fault has been detected in a location that could effect transmitter 
operation, and is user-addressable. To correct this problem, use a HART 
Communicator to interrogate and reconfigure the appropriate portion of the 
transmitter memory. Contact Rosemount Nuclear Instruments, Inc. at 
(952) 949-5210 if you need assistance.
Warnings
Warnings appear on the LCD meter display to alert you of user-repairable 
problems with the transmitter, or current transmitter operations. Warnings 
appear alternately with other transmitter information until the warning 
condition is corrected or the transmitter completes the operation that warrants 
the warning message.
PRESS LIMIT
The process variable read by the transmitter is outside of the transmitter’s 
range.
TEMP LIMIT
The secondary temperature variable read by the transmitter is outside of the 
transmitter’s range.
CURR SATURD
The pressure read by the module is outside of the specified range, and the 
analog output has been driven to saturation levels. See “Failure Mode Alarm” 
in Section 2.
LOOP TEST
A loop test is in progress. During a loop test or 4–20 mA trim, the analog 
output is set to a fixed value. The meter display alternates between the 
current selected in milliamps and “LOOP TEST.”
XMTR INFO
A non-volatile memory fault has been detected in the transmitter memory by 
the memory verification routine. The memory fault is in a location containing 
transmitter information. To correct this problem, use a HART Communicator to 
interrogate and reconfigure the appropriate portion of the transmitter memory. 
This warning does not effect the transmitter operation. Contact Rosemount 
Nuclear Instruments Inc. at (952) 949-5210 if you need assistance.