Emerson 3051N User Manual

Page of 100
Reference Manual
00809-0100-4808, Rev CA
June 2008
Rosemount 3051N
A-4
Table A-1.  Typical HART Fast Key Sequences for the Rosemount 3051 (partial listing).
Function
HART Fast Key Sequence
Alarm and Saturation Levels
1, 4, 2, 7
Analog Output Alarm Type
1, 4, 3, 2, 4
Custom Meter Configuration
1, 3, 7, 2
Custom Meter Value
1, 4, 3, 4, 3
 Damping
1, 3, 6
Date
1, 3, 4, 1
Descriptor
1, 3, 4, 2
Digital To Analog Trim (4–20 mA Output)
1, 2, 3, 2, 1
Disable Local Span/Zero Adjustment
1, 4, 4, 1, 7
Field Device Info
1, 4, 4, 1
Full Trim
1, 2, 3, 3
Keypad Input – Rerange
1, 2, 3, 1, 1
Local Zero and Span Control
1, 4, 4,1, 7
Loop Test
1, 2, 2
Lower Sensor Trim
1, 2, 3, 3, 2
Message 
1, 3, 4, 3
Meter Options
1, 4, 3, 4
Number Of Requested Preambles
1, 4, 3, 3, 2
 Range Values
1, 3, 3
Rerange
1, 2, 3, 1
Scaled D/A Trim (4–20 mA Output)
1, 2, 3, 2, 2
Self Test (Transmitter)
1, 2, 1, 1
Sensor Info
1, 4, 4, 2
Sensor Temperature
1, 1, 4 
Sensor Trim Points
1, 2, 3, 3, 5
Status
1, 2, 1, 2
 Tag
1, 3, 1
 Transfer Function (Setting Output Type)
1, 3, 5
Transmitter Security (Write Protect)
1, 3, 4, 4
Trim Analog Output
1, 2, 3, 2 
 Units (Process Variable)
1, 3, 2
Upper Sensor Trim
1, 2, 3, 3, 3
Zero Trim
1, 2, 3, 3, 1
NOTE
A check (
✔) indicates the basic configuration parameters. At minimum, 
these parameters should be verified as part of the configuration and
startup procedure.