Emerson 3051N User Manual

Page of 100
Reference Manual
00809-0100-4808, Rev CA
June 2008
Rosemount 3051N
A-14
Fast Key Sequences
The Fast Key sequence is a sequence of numerical button presses, 
corresponding to the menu options that lead you to a given task. Use Table 
A-1, an alphabetical listing of most on-line functions, to find the corresponding 
HART fast key sequences. These codes are applicable only to Rosemount 
3051N transmitters and the HART Communicator.
Hot Key options
The Hot Key menu is a user-definable menu that can store shortcuts for up to 
20 of your most frequently performed tasks. For example, if you change 
device tags, and damping often, you can add options for these functions to 
the Hot Key menu. Once you are Online, the Hot Key will automatically 
appear in the toolbar. To add a custom option to the Hot Key menu, refer to 
the Rosemount 375 Communicator user manual.
To use a Hot Key option, you must first properly connect the Rosemount 375 
Field Communicator to a device. You can access the Hot Key menu from any 
online window. To use a Hot Key option:
1.
Connect the Rosemount 375 Field Communicator to a HART loop or 
device.
2.
Tap the Hot Key. The Hot Key menu is displayed.
3.
Double-tap the desired option.
DIAGNOSTIC 
MESSAGES
The following pages contain a list of messages used by both of the 
Rosemount 275 and Rosemount 375 HART Communicators (HC) and their 
corresponding descriptions.
Variable parameters within the text of a message are indicated with
<variable parameter>.
Reference to the name of another message is identified by 
[another message].
Message
Description
1k snsr EEPROM 
error-factory ON
Return to Rosemount Nuclear Instruments, Inc. for repair.
1k snsr EEPROM 
error-user-no out ON
Use the HART communicator to reset the following parameters: 
remote seal isolator, remote seal fill fluid, flange material, o-ring 
material, transmitter type, remote seal type, flange type, meter 
type, number of remote seals.
1k snsr EEPROM
error-user ON
Perform a full trim to recalibrate the transmitter.
4k micro EEPROM 
error-factory ON
Return to Rosemount Nuclear Instruments, Inc. for repair.
4k micro EEPROM 
error-user-no out ON
Use the HART communicator to reset the message field.
4k micro EEPROM 
error-user ON
Use the HART communicator to reset the following parameters: 
units, range values, damping, analog output, transfer function, 
tag, scaled meter values. Perform a d/a trim to ensure that the 
error is corrected.
4k snsr EEPROM
error-factory ON
Return to Rosemount Nuclear Instruments, Inc. for repair.
4k snsr EEPROM
error-user ON
Use the HART communicator to reset the temperature units 
and the calibration type.