When installing the battery charger as a replacement part, it is necessary to verify the proper charger 
settings and adjust as necessary.
1.  Incoming AC voltage 115 or 230 volts.
2.  Battery voltage - 12 or 24 volts DC.
3.  Battery type - Lead Acid / Ni-Cad 9 or 18 Cell / Ni-Cad 10 or 20 Cell.
If battery charger is powered with the incorrect settings, damage to the charger and/or batteries may occur.
The Firetrol® battery charger features a fully automatic 4 step charging cycle.  The charging cycles are as 
indicated:
Step 1: Qualification Stage (Flashing yellow and green LEDs)
 
During this stage, the battery charger checks the batteries to insure they can accept a fast charge.  
 
It also checks for missing or defective batteries.  If the charger detects missing or defective batteries  
 
a fault will be given (solid red LED).
Step 2: Fast Charge (Solid yellow LED)
 
Charges the batteries until they reach peak voltage.
Step 3: Bulk Charge (Solid yellow LED and slow blinking green LED)
 
Charges the batteries at a constant potential of peak voltage until current reaches 500mA.
Step 4: Float Charge (Solid green LED)
 
Trickle charges the batteries to maintain peak potential.
• Charger reset push-button (resets charging cycle to beginning)
BATTERY CHARGER