Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual
Section 1: Introduction
3-9000-765 Rev D
March 2013
Meter specifications
 15
Electronic specifications
Power
Meter
10.4 VDC to 36 VDC measured at the meter terminals
1
11 W maximum power consumption
Serial cable
Belden #9940  or equivalent (22 gauge)
Capacitance (pF/m) 121.397 (conductor to conductor) 
Capacitance (pF/m) 219.827 (conductor to other conductor and shield)
Resistance (DC) DCR @ 20 °C (Ohm/km) 48.2307 
Nominal Outer shield resistance - DCR @ 20°C (Ohm/km) 16.405
Operating voltage - 300 V RMS (UL AWM Style 2464)
Current  2.4 Amps  per conductor @ 25°C (recommended)
Ethernet cable 
Cat-5 Standard  100Mbps
Frequency (
)
22 AWG wire characteristics are as follows:
Capacitance = 20 pF/ft or 20 nF/1000 ft (between two wires)
Resistance = 0.0168 Ohms/ft or 16.8 Ohms/1000 ft
Pull-up voltage is 24 VDC
Temperature
flameproof transmitter  
electronic enclosure and 
base electronic enclosure
Ambient:   -40 
o
F to 140 
o
F (-40 
o
C to 60 
o
C)
Storage:     -58 
o
F to 185 
o
F (-50 
o
C to 85 
o
C) 
Note:   The transmitter electronics enclosure and base enclosure must be remote mounted if the 
operating temperature exceeds 140 
o
F (60 
o
C).
Transducers 
LT-10 and LT-11 Operating temperature range with NBR O-rings 
-58 
o
F to +275 
o
F (-50 
o
C to 135 
o
C)
LT-10 and LT-11 Operating temperature range with FKM O-rings  
         -40 
o
F to +302
 o
F (-40 
o
C to +150 
o
C) 
Note:  The process temperature must not exceed the operating temperature range of  
the transducers.
Note:  LT-10 transducers are designed for 4 inch to 10 inch meters. LT-11 transducers are designed 
for 12 inch and larger meters. 
Note:  The ultrasonic transducers are not intended for use across boundary walls of different 
hazardous area classifications. The transmitter electronics cannot be remote mounted from 
a Division 1 classification to a Division 2 area to meet an area classification.
Acquisition Cable
Total cable length between the Acquisition Module and ultrasonic transducers must not 
exceed 15 feet (4.7 meters) when using the remote mount option (
)
Table 1-2  Meter specifications