Alarm Delay: The amount of time the F3400/F1000 waits to send an alert after an alarm 
condition is detected. The F3400/F1000 uses this same time delay to report a return to normal 
after the alarm condition clears. The alarm delay is active for all input types except Not 
Configured. 
Example: 
An input is configured as a digital NO, labeled “CRAC UNIT ALARM” and has an alarm 
delay of 10 seconds. When the CRAC unit alarms, it closes the contact to the F3400/F1000. 
If the CRAC unit returns to normal and opens the contact to the F3400/F1000 within the 10 
second alarm delay, no alarm is generated in the F3400/F1000. If the CRAC unit remains in 
alarm for 10 seconds or more, the F3400/F1000 records the alarm and generates notification 
per the input settings.   If the CRAC unit returns to normal and alarms within the 10 second 
alarm delay, the F3400/F1000 does not record it as a return to normal. Once the CRAC unit 
returns to normal for the 10 second alarm delay, the F3400/F1000 records a return to normal 
and generators notification per the F3400/F1000 settings.
Hysteresis: The number that designates the amount an input reading must sway from its preset 
alarm reading before it is classified as returned to normal.   The Hysteresis provides a deadband 
around the limit settings to prevent several alarms and return to normal alarms when the input is 
the same as a limit setting.
The Hysteresis applies when the input type is Analog 4-20mA or thermistor and is active for 
High Limit 1, High Limit 2, Low Limit 1 and Low Limit 2.
Example: 
A temperature sensor alarms when it reaches its High Limit 1 of 80°F. If Hysteresis is set at 
four, the sensor must register less than 76°F before the F3400/F1000 reports it as returned to 
normal. In another example, a humidity sensor alarms when it reaches its Low Limit 2 of 
30% RH. If the Hysteresis is set at five, the humidity must register more than 35% before the 
F3400/F1000 reports it as returned to normal.
Relay Activate: Used to assign a Threshold change to analog inputs, or Digital Alarm 
generated by this input to a specific relay. To select the relay, check the relay box. This feature 
can be set to activate on a High 2/Low 2 threshold for analog points, in the Relay configuration 
menu 
Dial Out Notification: The list of up to 4 pager numbers to which the F3400/F1000 sends 
alarm notification. The numbers correspond to phone numbers configured from the Configure 
Phone Number links at the bottom of the Modem Configuration page. Separate each ID number 
with a comma. Enter zero to disable. The F3400/F1000 will dial the lowest number listed 
regardless of the order the numbers are listed. See 4.5.1, “Configure Phone Numbers” on 
Example: 
If the Alarm dial out string is set to “3, 5, 1, 0”, the F3400/F1000 will dial Pager #1, Pager #3 
and then Pager #5 when an alarm occurs. Pager notification will be sent when an input 
alarms (high limit 2, high limit 1, low limit 1, low limit 2 is exceeded or the digital input is in 
alarm). An option on the Pager Configuration page determines if the F3400/F1000 will send 
a page when an input returns to normal.