Falcon F1000 User Manual

Page of 94
www.rletech.com
43
970.484.6510
4
  Configuration Menu
4.5. Modem
The Modem link allows users to configure the F3400-M/F1000’s internal modem (if the option 
is available). This instructs the F3400-M/F1000-M when, how, and whom to call when an 
alarm occurs. See definitions below for more information.
Figure 4.7 Modem Configuration Page
Initialization String: A maximum of 38 characters. &c1 and &d3 are mandatorys0=1 sets 
the modem to answer after one ring. s0=0 disables the auto answer and prevents dial-in access. 
Dial Prefix:   Should be a specific Hayes compatible command or dial modifier depending on 
pager requirements. It is also limited to 38 characters. The default is set to atdt.
Pager Deliveries: Designates the number of times (0-255) the pager is called until the alarm is 
acknowledged. Pagers are called in sequence. For example, if Pager Deliveries is set to 3 and 
pagers 1, 7, and 10 are programmed to be notified, the F3400/F1000 dials 1, 7, 10, 1, 7, 10, 1, 7, 
10. As soon as the alarm is acknowledged, the F3400/F1000 quits dialing the pagers with that 
particular access code. Pagers with different access codes are still dialed.
Pager Interval: Determines the number of minutes to wait between redials.
Pager Baud Rate: Allows the user to set the pager communications settings. 
Pager Resend: Select yes for the F3400/F1000 to send all unacknowledged alarms in the 
Alarm History Menu. Select no to send only the last unacknowledged alarm. If no is selected, 
the F3400/F1000 will auto-acknowledge all alarms associated with that particular pager once a 
successful page has occurred.
Modem Password: Defines a remote access password, seven characters maximum. Used when 
remotely logging into the F3400/F1000 through a modem.
Redial Attempts: Determines the number of times (1-255) to call a number until the call is 
successful. Enter 0 to disable this function.