APC Symmetra SYCF160KH User Manual

Page of 44
Configure Output Relays
1.
Select Environment and press ENTER.
UPS
Alarms
Power Dist
Log
Switch Gear
Admin
→ Environment
Help
2.
Select Output Relays and press ENTER.
Input Contacts
→ Output Relays
Alarm Relay Map
3.
Select desired output relay, 1 through 4, select
Configuration, and press ENTER.
Input Contact:xof4
<relay name>
Status: Closed
→ Configuration
4.
Change the settings for name and normal
position for the selected output relay.
Relay x Name
<output relay>
Normal: Closed
990–3015E-001
Symmetra™ PX48, 96, and 160 kW 400 V 100 kW 208 V Operation
23