ACDelco AC-G0005 User Manual

Page of 36
Electrical Device 
Rated (Running) Watts 
Additional Surge Watts 
air compressor (1 HP) 
1500 
3000 
air compressor (1 - 1/2 HP) 
2500 
2500 
airless sprayer (1/3 HP) 
600 
1200 
box fan 
300 
600 
clock radio AM/FM 
300 
coffee maker 
1500 
computer w/17 inch monitor 
800 
deep freezer 
500 
500 
electric drill (1/2 HP) 
1000 
1000 
DVD/CD player or VCR 
100 
furnace fan blower (1/2 HP) 
800 
1300 
garage door opener (1/2 HP) 
480 
520 
hot plate 
2500 
light bulb (75 watt) 
75 
microwave oven (1000 watt) 
1000 
quartz halogen work light 
1000 
refrigerator/freezer (18 Cu. Ft.) 
800 
1600 
saw - circular (7 1/4 inch) 
1500 
1500 
saw - miter (10 inch) 
1800 
1800 
saw - radial arm 
2000 
2000 
saw - reciprocating 
960 
1040 
saw - table/radial (10 inch) 
2000 
2000 
security system 
180 
stereo receiver 
450 
electric stove - single element 
1500 
sump pump 
800 
1200 
table planer (6 inch) 
1800 
1800 
television (27 inch color) 
500 
electric water heater (40 gallon) 
4000 
well water pump (1/3 HP) 
1000 
2000 
window air conditioner (10000 BTU) 
1200 
1800 
window fan 
300 
600 
Figure 7 - Estimated wattage requirements for common electrical devices.  
 
Connect electrical devices to this generator according to the following procedure: 
1. Allow the engine to run for several minutes after it has been started. 
2. Confirm that the electrical device is switched off prior to plugging it into this generator. 
 
                                                                                
   
Connect only electrical devices that are in good working order. Faulty devices or power cords present the risk of electrical shock. 
Immediately turn off and disconnect any device that commences to operate abnormally, sluggish or abruptly stops. Determine if the 
problem was the device or the rated load capacity of this generator has been exceeded. 
 
NOTE: Plug appliances into the correct outlet. Connect standard 120 Volt, single phase, 60 Hz loads to the 120 Volt outlet. Connect 240/120Volt, 
single phase, 60Hz loads with a NEMA L14-30 plug only to the 240/120 Volt outlet. See Figure 8 for an illustration of these outlets. 
 
                                                                                
   
Even though this ACDelco Model AC-G0005 Portable Generator has an overall rated wattage of 6000, do not attempt to draw more than 
6400 Watts (20 A) from any ONE of the 120 Volt outlets. Draws higher than 6400 Watts (20 A) will damage this generator and void the 
warranty.
 
 
3. Switch the circuit breaker to the “on” position. 
 
NOTE: While this generator is running, power is available from either the standard 120 Volt outlets or the 240/120 Volt NEMA outlet. Both 120 Volts 
and 240 Volts can be simultaneously drawn from this generator. 
 
4. Turn on the connected electrical devices beginning with the device with the highest rated wattage requirement and then each additional device 
with the next lower rated wattage requirement. 
 
Model AC-G0005 6500 Surge Watts / 6000 Running Watts Electric Start Portable Generator 
17