Delta Tau GEO BRICK LV User Manual

Page of 271
Geo Brick LV User Manual
 
Troubleshooting 
 258 
Enabling ModBus 
A Brick unit ordered initially with the ModBus option is normally enabled by factory.  
However,  ModBus  is  a  field  upgradeable  option.  The  user  needs  to  provide  Delta  Tau  (or  their  local 
distributor) with the MAC ID of the Brick unit. This is found in the lower left hand side of the Ethernet 
100 Base T utility. Upon purchase of the ModBus Option, a .BIN file is obtained from Delta Tau for this 
purpose. Installing this feature successfully requires the following procedure: 
 
Step1:
  Hold the BOOT SW switch button down 
 
Step2:  Click on ModBus Option. The utility will prompt for the .bin file. 
 
MAKE SURE you open the correct file. 
 
 
 
 
 
Step3: Release the BOOT SW switch button after the ModBus unlocked message is generated. 
 
 
Step4:  Click on Done, and recycle logic power (24V) on the Brick