Turbo PMAC Motor Setup Flowchart 
Initial Setup Parameters 
Activating the Motor: Ixx00 
The Ixx00 motor activation parameter must be set to 1 for any motor that is to be used on Turbo PMAC.  It 
should be set to 0 for any motor that is not used, so Turbo PMAC will not waste computation time on that 
motor.  An activated motor can be enabled or disabled; a de-activated motor is not monitored in any way. 
Activating PMAC Motor Commutation: Ixx01 
Bit 0 of the Ixx01 commutation-enable parameter must be set to 1 if Turbo PMAC is performing the 
commutation and/or digital current-loop closure for the motor.  It must be set to 0 for any motor if Turbo 
PMAC is performing neither the commutation nor digital current loop for the motor.  If commutation is 
enabled, variables Ixx70 – Ixx84 for the motor must be set to specify how the commutation is done.  The 
instructions for setting these variables are given in the Commutation section of this manual.