PLANNING YOUR INSTALLATION 
 
PAGE 6 
REDUCED MASONRY STRUCTURE CLEARANCE 
(ALCOVE) 
Your Earth Stove can be installed in a masonry struc-
ture with reduced clearances if the structure was built to 
National Building Code for fireplaces and chimneys 
(UBC 37). 
 
The firebox of the masonry structure must be of ade-
quate size to allow a minimum of 6" (152 mm) clear-
ance to the sides and top of the stove and 2" (51 mm) 
clearance to the rear. All stove models must be installed 
on their original listed legs or base unless otherwise 
specified by OMNI Testing Laboratory. 
 
FLOOR PROTECTION
 
This appliance requires a non-combustible floor protection for 
ember protection.  If the floor protection is to be stone, tile, 
brick, etc., it must be mortared or grouted to form a continu-
ous non-combustible surface.  If a chimney connector ex-
tends horizontally over the floor, protection must cover the 
floor under the connector and at least 2" (51 mm) to either 
side. 
 
The floor protection must extend completely beneath the 
stove and to the front, sides, and rear as indicated: 
 
USA Requirements 
16” (406 mm) min. to the front of the fuel door glass 
8” (203 mm) min. beyond the sides of the fuel door opening 
 
Canada Requirements 
18” (457 mm) min. to the front of the fuel door glass 
8” (203 mm) min. beyond the sides of the stove body 
 
STANDARD PARALLEL HEARTH PAD SHOWN 
 
 
 
PROTECTED WALL CLEARANCE 
Some local codes will allow reduced clearances when the 
stove is installed adjacent to a protected wall system. The 
variance must be approved by your local building official. 
Normally, the protected wall system is defined as a non- 
combustible material with a minimum of 1" (25.4 mm) air 
space behind. Check your local building codes or with a 
qualified installer (Ref. NFPA 211). 
 
OUTSIDE AIR 
In all manufactured (mobile) homes and in many site built 
residences (subject to local code), a stove may be required 
to use outside air for combustion. A 3” (76 mm) diameter 
outside air floor duct is available through your dealer. 
 
 
 
This appliance utilizes a 3" (76 mm) diameter outside air 
floor duct (Catalog # 14M66). Outside air can be taken from 
beneath the home or through an outside wall. The collar for 
connecting flex to stove in on the underside of the stove as 
shown here. 
 
18” (457 mm) – Canada 
16” (406 mm) - USA 
8” (203 mm)
Canada
 
8” - USA 
0” - USA  
8” – Can.
 
8” (203 mm)
Canada
8” - USA