HORIZONTALLY THROUGH WALL 
(refer to Figure 9) 
 
NOTE: Follow L-Vent chimney 
manufacturer’s instructions. 
 
1. 
Position stove, adhering to 
clearances shown in Figures 1 & 2. 
 
2. 
Locate position of hole in wall; 
directly behind stove exhaust vent 
(refer to figure 5). 
 
3. 
Always maintain 3” clearance from 
combustible materials. 
 
4. 
Install L-Vent wall thimble per L-Vent 
manufacturer’s instructions. 
 
5. 
Attach enough piping to penetrate 
and extend at least 6” beyond 
exterior walls. A minimum 8-foot 
vertical pipe run is suggested where 
possible to reduce the possibility of 
smoke spillage in the event of a loss 
of negative pressure. 
 
6. 
Attach cap and seal outside wall 
thimbles with non-hardening 
waterproof mastic. 
 
7. 
Termination should not be located so 
that hot exhaust gases can ignite 
trees, shrubs, or grasses or be a 
hazard to children. Exhaust gases 
can reach temperatures of 500ºF and 
cause serious burns if touched. 
 
 
 
 
Locate terminations: a) not less than 3 feet above any forced air inlet 
located within 10 feet; b) not less than 4 feet below or horizontally from, or 
one foot above, any door, window or gravity air inlet into any building; c) not 
less than two feet from an adjacent building and not less than 7 feet above 
grade when located adjacent to a public walkway. Mobile home installations 
must use a spark arrester. 
 
 
 
 
 
 