Bosch Appliances Smoke Alarm D2071A User Manual

Page of 28
23
Bosch | 09/04 | 74-06200-000-F
5.0
Receiver Reports
D2071A  | Operations & Installation Guide | 5.0    Receiver Reports
 
Title Description 
ALARM ZN 1 
Closure or short between the two loops of the Class “A” Alarm Initiating Circuit. This report is delayed 
by the time specified in Retard Time (for waterflow alarm applications only). 
ALARM ZN 2 
Mode 1: Open on the Class “B” Supervisory Circuit (Terminals 10 and 11). 
Mode 2: Resistance on the Class “B” Supervisory Circuit (Terminals 10 and 11). 
Mode 3: Closure or short between terminals or a ground fault on the positive (+) side of the Class “B” 
Supervisory Circuit (Terminals 10 and 11). 
ALARM ZN 3 
Mode 1: Open on the Class “B” Supervisory Circuit (Terminals 10 and 11). 
Mode 2: Resistance on the Class “B” Supervisory Circuit Terminals 10 and 11). 
Mode 3: Closure or short between terminals or a ground fault on the positive (+) side of the Class “B” 
Supervisory Circuit (Terminals 10 and 11). 
RESTORAL ZN 1 
The Class “A” Alarm Initiating Circuit returned to normal from an alarm or trouble condition. This report is 
delayed by the time specified in Reset Time when the circuit restores from an alarm condition. 
RESTORAL ZN 2 
All modes: Trouble or alarm condition on Zone 2 cleared. 
RESTORAL ZN 3 
All modes: Trouble or alarm condition on Zone 3 cleared. 
RESTORAL ZN 9 
12 VAC Mode: Report is transmitted after AC power is restored, the control panel is programmed, or 
the battery is changed or recharged. 
24 VDC Mode: Report is transmitted when the DC power input is applied, when the DC power input 
reaches 27.6 VDC after falling below 24.3 VDC, or after programming the control panel. 
RESTORAL ZN B 
Primary phone line restored. 
RESTORAL ZN C
Alternate phone line restored. 
RESTORAL ZN E 
Normal test timer activation. 
TROUBLE ZN 1 
Break or ground on either loop of the Class “A” Alarm Initiating Circuit (no retard time applies). 
TROUBLE ZN 2 
Mode 1: Not available. 
Mode 2: Class B circuit, Terminals 10 and 11, open. 
Mode 3: Class B circuit, Terminals 10 and 11, open. 
TROUBLE ZN 3 
Mode 1: Not available. 
Mode 2: Class “B” Supervisory Circuit, Terminals 11 and 12, open. 
Mode 3: Class “B”  Supervisory Circuit, Terminals 11 and 12, open. 
TROUBLE ZN 9 
12 VAC Mode: Low battery 
24 VDC Mode: DC power input less than 24.3 V 
TROUBLE ZN B 
Open or short on primary telephone line. 
TROUBLE ZN C 
Open or short on alternate telephone line. 
TROUBLE ZN E 
Communications failure after ten attempts to transmit a report. The reports in the D2071A buffer when a 
communications failure occurs are not transmitted. The buffer is cleared. 
or 
Test timer failed to report on the first attempt. 
or 
When received in the same transmission (telephone call) with another report, indicates the other 
report(s) in the transmission did not get through on the first attempt. 
 
Table 10:
Receiver  Reports