80 | Accessories for Control Panels and Keypads | Expansion Modules
DS7465i Input‑Output
Module
Features
▶ Supervises one power-limited input zone
▶ Provides one output relay
▶ Can be used in UL Listed fire and security applications
▶ DIP switch programmable
The DS7465i Input-Output Module works with compatible
multiplex systems and uses two multiplex zone addresses.
It supplies a DIP switch programmable Form C relay (output
zone) that activates on several different system events. The
DS7465i Module provides an input zone for monitoring
conventional normally-open (NO) or normally-closed (NC)
contacts. The module reports the contact status as a
multiplex address to the control panel. Use up to sixty
DS7465i Modules with compatible control panels or
multiplex expansion modules.
Functions
Supervised Input Zone
The power-limited input zone is designed to monitor NO or
NC dry contacts. It is supervised using 47 kΩ end-of-line
(EOL) resistors.
Output Relay
Use the output relay only on power-limited circuits. The
relay contacts are rated 1 A at 30 VDC for resistive loads.
Do not use the output relay with inductive or capacitive
loads.
Certifications and Approvals
Region
Certification
Europe
CE
89/336/EEC, EN55022: 1998,
EN50130-4: 1995, EN60950: 2000,
EN61000-3-2, EN61000-3-3,
EN61000-4-2, EN61000-4-3,
EN61000-4-4, EN61000-4-5,
EN61000-4-6, EN61000-4-11
USA
UL
NBSX: Household Burglar Alarm System
Units (UL1023), UOXX: Control Unit
Accessories, System (UL864, 9th edition),
UTOU: Control Units and Accessories -
Household System Type (UL985)
CSFM
7165-1615: 113, 7165-1615: 119,
7170-1615: 144, and 7170-1615:
145   July 2008
Installation/Configuration Notes
Compatibility Information
Control Panels
D9412GV2, D7412GV2, and D7212GV2 Control
Panel
D9412G, D7412G, and D7212G Control Panel
D9124 Fire Alarm Control Panel
DS7400Xi Control Panel
Multiplex Modules
D8125MUX Multiplex Bus Interface
DS7430 Multiplex Expansion Module
DS7436 Multiplex Expansion Module
The DS7465i Series Modules require a multiplex expansion
module to connect to the control panels.
Fire Applications
For UL Listed fire installations, normally-open (NO)
contacts must be used. For fire installations, order
Multiplex-zone Fire EOL resistors (P/N: 28010) in the
quantity needed.
Wiring
Maximum Impedance: 4.05 Ω at +20°C (+68°F) nominal
Distance (approximate)
Size
76 m
0.65 mm
193 m
1.02 mm
250 ft
22 AWG
600 ft
18 AWG
Refer to the multiplex expansion module’s reference guide for
multiplex wiring requirements.
The recommended wiring to the control panel is quad (four-
wire) cable. Do not use shielded or twisted pair cable.
Note
If used in fire applications, 18 AWG wire is
required.
Bosch Security Systems B.V. 
 www.boschsecurity.com