2. ACCEPTABLE CLEARANCES: 
 
Due to intense heat generated by radiation, above the grate level only non-combustible construction 
should be provided. In USA and Canada these broilers should be installed in non-combustible 
locations only. 
 
(i) 
Minimum Clearance from Non-Combustible Construction (in European Community 
Countries and North America).  
 
 
Right 
 
Left  
 
Back      
 
Floor 
 
 
 
 
4" (100 mm) 
 
(ii) 
Minimum Clearance from Combustible Construction (in European Community Countries 
Only) 
 
 
Right 
 
Left 
 
Back 
 
Floor 
 
250 mm 
 
250 mm 
 
250 mm 
 
150 mm 
 
 
 
3. GAS CONNECTION:
 
 
The gas pressure regulator supplied must be installed at the gas inlet of each broiler. Each 
regulator is adjusted to yield a pressure of 3.5" water column (9 mbar) for natural Gas or 10" water 
column (25 mbar) for Propane or Butane gas. No pressure regulator is required for propane gas in 
Canada. 
 
Recommended minimum gas supply lines are listed below for units with: 
 
 
7 Burners or less: 
 
3/4" (19 mm)
 
8 Burners and more: 
 
1" (25.4 mm)
 
Gas supply pressures in the European Community Countries should be as shown below: 
 
Gas Type 
Supply Pressure 
G20 20 
mbar 
G25 25 
mbar 
G20/25 20/25 
mbar 
G30 
30 or 50 mbar depending on country 
G31 
30, 37 or 50 mbar depending on country 
 
A shut-off valve in a readily accessible location must be installed on the gas supply line before 
connecting it to the unit. 
 
When making gas pipe connections, only pipe joint compound resistant to the action of liquefied 
petroleum gases should be used. 
 
 
 
 
4