Compressor runs, but evaporator does not
1.  Faulty blower 
motor or broken wire 
connection
•  Evaporator coil probably frozen
•  Shut off power to condensing unit
•  Call a CERTIFIED HVAC service technician for repair
2.  Defective low 
pressure switch not 
shutting compressor off 
when pressure drops
•  Compressor would continue to run when thermostat is 
satisfied and shuts blower and solenoid off. When space 
warms up to set point, blower starts and the system 
runs normally.
•  Prolonged running without refrigerant flow will 
damage or destroy compressor. If this condition exists, 
call a CERTIFIED HVAC service technician.
Compressor short cycles, which is different from running intermittently
1.  System pressure 
controls defective.
Call a CERTIFIED HVAC service technician to verify and 
repair.
2.  System low on 
refrigerant.
Observe for flashing in refrigerant sight glass located in 1/4” 
copper tube at condensing unit. If flashing with bubbles, 
call a CERTIFIED HVAC service technician for leak location, 
repair, and adding refrigerant.
3.  Condenser fan motor 
defective
•  Fan does not run with compressor.  
•  ¼” Copper tube at sight glass – very hot, compressor 
very hot, runs short time, shuts off.
•  Shut power off to condensing unit
•  Call a CERTIFIED HVAC service technician for repair.
4.  Compressor starting 
components defective.
•  Compressor very hot and hums when trying to start.
•  Shut power off to condensing unit.
•  Call a CERTIFIED HVAC service technician.
Evaporator coil freezes
1.  Air filter, if equipped, 
dirty
Clean or replace filter
2.  Evaporator coil and/
or blower dirty
Clean coil and blower
3.  Thermostat set point 
too low.
Set point should not be lower than 50°. If so, increase to 
above 50°
4.  System low on 
refrigerant
Check refrigerant “sight glass” in 1/4” tubing. Check for bubbles 
after system has run for several minutes. If bubbles present, 
call a CERTIFIED HVAC service technican. If sight is clear of 
bubbles, refrigerant level is OK.