Westinghouse WBCNG399WPU Installation Instruction

Page of 90
41 
 
 
 
WHL-016 REV. 3.4.15 
b. For example: If the 
3” exhaust vent has two short 90
o
 elbows and 
10 feet of PVC pipe we will calculate: Exhaust Vent Equivalent Length 
= (2x5) + 10 = 20 feet. 
 
Further, if the 
3” intake pipe has two short 90
o
 elbows, one 45
o
 elbow, 
and 10 feet of PVC pipe, the following calculation applies: Intake Pipe 
Equivalent Length = (2x5) + 3 + 10 = 23 feet. 
 
The Exhaust Vent Equivalent Length + the Intake Pipe Equivalent 
Length equal the Total Equivalent Length. In this example, the Total 
Equivalent Length is 43 feet. 
 
c. The minimum Total Equivalent Length is 15 feet. 
F. LONGER VENT RUNS 
The maximum total equivalent length can be extended by equally increasing the diameter of both the exhaust vent and intake pipes. 
However, the transitions should begin a minimum of 16 total equivalent feet from the boiler. 
 
On all units EXCEPT the 285 model, maximum equivalent length for increased diameter vent pipes is 275 ft, which includes the 16 ft 
from the boiler with a transition total of 259 ft upsize piping for longer vent runs (234 ft for the 285). On the 285 model, the maximum 
equivalent length for increased diameter vent pipes is 250 ft., which includes the 16 ft from the boiler with a transition total of 234 ft 
upsize piping for longer vent runs. 
 
VENT TRANSITION FITTING 
SIZE 
REDUCING COUPLING 
FINAL VENT SIZE 
3” Venting 
4” x 3” 
4” 
4” Venting 
6” x 4” 
6” 
Table 12 
 
Do not exceed the maximum lengths for increased diameter vent pipes. Excessive length could result in appliance shutdown and 
property damage. 
G. EXHAUST VENT AND INTAKE PIPE INSTALLATION 
 
All joints of positive pressure vent systems must be sealed completely to prevent leakage of flue products into living space. 
 
1. Use only solid PVC or CPVC pipe, AL29-4C Stainless Steel, or a Polypropylene vent system, approved for use with Category IV 
boilers. 
 
FOAM CORE PIPING IS NOT APPROVED FOR EXHAUST APPLICATIONS. Foam core piping may be used on air inlet piping only
 
2. Remove all burrs and debris from joints and fittings. 
 
3. When using PVC or CPVC pipe, all joints must be properly cleaned, primed, and cemented. Use only cement and primer approved 
for use with the pipe material. Cement must conform to ASTM D2564 for PVC and ASTM F493 for CPVC pipe. NOTE: DO NOT 
CEMENT POLYPROPYLENE PIPE.
 
 
4. Ensure the vent is located where it will not be exposed to prevailing winds. 
 
5. In all roof venting applications, exhaust discharge must point away from the pitch of the roof. 
 
6. If the exhaust vent is to be terminated in a walled off area (such as a roof with a parapet wall), ensure the exhaust vent terminates a 
minimum of 10' from nearest wall and extends level with or above the top of the wall. This will ensure flue gas does not get trapped and 
possibly recirculated into the intake air pipe, which could contaminate the combustion air. 
 
7. To prevent water leakage, install adequate roof flashing where the pipe enters the roof. 
 
8. Do not locate vent over public walkways, driveways, or parking lots. Condensate could drip and freeze, resulting in a slip hazard or 
damage to vehicles and machinery. 
 
9. Due to potential moisture build-up, sidewall venting may not be the preferred venting option. To save time and cost, carefully 
consider venting installation and location. 
Figure 18