Westinghouse WBCNG399WPU Installation Instruction

Page of 90
53 
 
 
 
WHL-016 REV. 3.4.15 
D. LINE VOLTAGE WIRING FOR STANDARD BOILER 
NOTE: A termination plug is included in the CAT 3 / CAT 5 Bus Connection Point, labeled J3 in Figure 29. DO NOT REMOVE THIS 
PLUG! Doing so will affect boiler operation and void warranty. 
 
1. Connect the incoming power wiring to the line voltage terminal strip in the electrical junction box at terminals 120V, Neutral, Ground 
(shown in Figure 29). 
 
2. A line voltage fused disconnect switch may be required, externally mounted and connected according to local codes that may apply. 
 
3. Connect the boiler pump as shown in Figure 29 to the terminals marked 1 
– (HOT), 2 – (NEUT), and 3 – (GND). The connections 
shown are suitable for a maximum continuous pump draw of 3 amps at 120 volts. If the pump requires more current or voltage than the 
120 volts supplied, an external motor starter or contactor 
will be required. 
E. ALARM CONNECTIONS 
The control includes a dry contact alarm output. This is an 
SPDT circuit, rated at 5 amps at 120 volts. This contact 
can be used to activate an alarm light or bell or notify a 
building management system if the boiler goes into a 
lockout condition. The circuit between the ALARM COM 
and NC terminals is closed during normal operation and 
the circuit between ALARM COM and NO is open during 
normal operation. The connections depicted in Figure 29 
show two 120 volt lights connected to the alarm terminals. 
One light will be on when the boiler is in normal mode and 
the other light will be on when the boiler is in lockout 
mode. 
 
NOTE: Isolate 120V wiring from 24V wiring to prevent any 
electrical “noise”. 
F. LOW VOLTAGE CONNECTIONS FOR 
STANDARD BOILER 
1. All low voltage cables should enter the electrical 
junction box through the provided knock out holes as 
shown in Figure 28. 
 
2. Connect all low voltage field devices to the low voltage 
terminal strip located in the electrical junction box. 
 
NOTE: When making low voltage connections, ensure no 
external voltage is present in the thermostat circuits. If 
external voltage is present, provide an isolated contact to 
prevent damage to the control. 
G. THERMOSTAT 
1. Connect the room thermostat to the terminals marked 
THERMOSTAT in the electrical junction box (see Figure 
29). Alternately, any dry contact closure across these 
terminals will cause the boiler to run. Take caution to 
ensure neither of the terminals becomes connected to 
ground. 
 
2. Mount the thermostat on an inside wall as central as 
possible to the area being heated, but away from drafts or 
heat producing devices such as television sets that could 
influence the ability of the thermostat to measure room 
temperature. 
 
3. If the thermostat is equipped with an anticipator and it is 
connected directly to the boiler, the anticipator should be 
set at 0.1 amps. If the thermostat is connected to other 
device(s), the anticipator should be set to match the power 
requirements of the device(s). See the instruction manual 
of the connected device(s) for further information. 
Figure 29 
– Boiler Control