Westinghouse WBCNG399WPU Installation Instruction

Page of 90
70 
 
 
 
WHL-016 REV. 3.4.15 
Press the 
▼ key once. 
FAULT HISTORY           8 
08/28/2009         Fr  5:19A 
This screen displays the eighth oldest lockout fault that occurred in the boiler controller. The top line will 
alternate between the words ‘FAULT HISTORY’ and the fault encountered. The bottom line displays the date 
and time the fault occurred.
 
Press the 
▼ key once. 
FAULT HISTORY           9 
08/28/2009         Fr  5:19A 
This screen displays the ninth oldest lockout fault that occurred in the boiler controller. The top line will alternate 
between the words ‘FAULT HISTORY’ and the fault encountered. The bottom line displays the date and time the 
fault occurred.
 
Press the 
▼ key once. 
FAULT HISTORY           10 
08/28/2009          Fr  5:19A 
This screen displays the tenth oldest lockout fault that occurred in the boiler controller. The top line will alternate 
between the words ‘FAULT HISTORY’ and the fault encountered. The bottom line displays the date and time the 
fault occurred.
 
Table 25 
– Fault History Screens 
B. CASCADE MENU 
This menu is accessed by pressing the  key from the default menu or the  key from the status menu. 
 
SCREEN 
DESCRIPTION 
CASCADE MASTER READY 
 
SYS   PUMP   OFF 
This screen tells the user that the boiler is configured as a Cascade Master Boiler and that the cascade system 
is ready to accept a demand for heat. The second line indicates the status of the system pump output of the 
cascade system. This screen will alternate with the default screen every 5 seconds or it can be accessed by 
pressing the  key from the default screen.
 
 
CASCADE  NO   FOLLOWER 
 
SYS   PUMP   OFF 
This screen is displayed when the boiler is configured as a Master Boiler and there are no connected follower 
boilers, or the follower boilers are not powered. The second line indicates status of the cascade system pump 
output. This screen will alternate with the default screen every 5 seconds or it can be accessed by pressing the 
 key from the default screen.
 
 
CASCADE  NO   SENSOR 
 
SYS   PUMP   OFF 
This screen is displayed when the boiler is configured as a Master Boiler and there is no system temperature 
sensor connected or the system sensor is defective. The cascade system will still function in this situation with 
reduced efficiency. All boilers will run simultaneously rather than in a staged fashion. The second line indicates 
the status of the system pump output of the cascade system. This screen will alternate with the default screen 
every 5 seconds or it can be accessed by pressing the  key from the default screen.
 
 
CASCADE  TT   0123  567 
 
SYS   PUMP   ON   12:47P 
Shows information about cascade status. The TT in the center of the top line shows that the cascade demand is 
coming from the TT contact being closed. You may also see DHW if the demand is from a DHW sensor, or 0-10 
if the demand is from a 0-10 volt input. The following numbers show which boiler addresses are currently 
communicating to the master. If a boiler address is not used or communicating, the number will not show on the 
display. In the example above, boiler address #4 is not communicating. When a boiler in the system is firing, its 
address number will alternate with a ‘.’  to signify it is firing. The bottom line shows the status of system pump 
output contacts.
 
Press the 
▼ key once. 
CASCADE  PWR          100% 
PRESENT   01234567 
This screen shows the overall cascade power output. The range of this value is the number of boilers 
communicating with the Master x 100. For example, if 8 boilers are connected and communicating, the 
maximum cascade power is 800%. The second line shows which boiler addresses are communicating with the 
Master.
 
Press the 
▼ key once. 
CASCADE  SYST            118
o
CASCADE  SET              190
o
F 
This screen shows the current system temperature sensor reading on the top line and the cascade system 
temperature setting on the bottom.
 
Press the 
▼ key once. 
BOILER  0                100% 
BOILER  1                  56% 
This screen shows the current cascade power demand output on a per connected boiler basis for boilers 
addressed as 0 and 1. In the screen above, boiler 0 is being commanded to fire at 100% and boiler 1 at 56%. If 
this were a 2 boiler 
system, the ‘CASCADE PWR’ screen above would read 156%.
 
Press the 
▼ key once. 
BOILER  2                  0% 
BOILER  3                  0% 
This screen shows the current cascade power demand output on a per connected boiler basis for boilers 
addressed as 2 and 3.
 
Press the 
▼ key once. 
BOILER  4                     0% 
BOILER  5                     0% 
This screen shows the current cascade power demand output on a per connected boiler basis for boilers 
addressed as 4 and 5.
 
Press the 
▼ key once. 
BOILER  6                     0% 
BOILER  7                     0% 
This screen shows the current cascade power demand output on a per connected boiler basis for boilers 
addressed as 6 and 7.
 
Table 26 
– Cascade Menu Screens 
C. BOILER TEST MODE 
This function is intended to simplify the gas adjustment. Listed in Table 27 are the recommended combustion settings for the gas type 
selected to run the boilers. Automatic modulation does not take place when the controller is in test mode. However, the boilers will 
modulate down if the program set point is reached while running in test mode. It is recommended you have the largest load possible to