TOSHIBA- 31
TX  Series
   48 - 1250A
5.1.12  System (Setpoint Page 12)
5.1.13  Calibration and Service (Setpoint Page 13)
Setpoint
Page
Security
Level
Description
Factory Setting
Default
Range
Section
Default Display Screen
Metering Data Page #
1
Enter Metering Page (1-4)
Metering Data Screen #
1
Enter Metering Screen
Page 1(1-10)
Page 2 (1-11)
Page 3 (1 - 29)
Page 4 (1 - 6)
Alarms
RTD Failure Alarm
Disabled
Enabled or Disabled
Thermal Register Alarm
90%
Off, 40-95%
Thermal Alarm Delay
10 sec
1-20 sec
Thermal Register Setup Info
Cold Stall Time
O/L Class
O/L Class (5-30) or  4-40 second time delay
Hot Stall Time
½ O/L Class
½ O/L Class, 4-40 sec
Stopped Cool Down Time
30 Min
10-300 Min
Runing Cool Down Time
15 Min
10-300 Min
Relay Measured Cool Rates
Disabled
Enabled or Disabled
Thermal Register Minimum
15%
10-50%
Motor Design Ambient Temp
40C
10-90C
Motor Design Run Temperature
80% Max
50-100% of  Motor Stator Max Temp
Motor Stator Max Temp
INS CLS
INS CLS, 10-240 C
I/B Input to Thermal Register
Enabled
Enabled Only
Use Calculated K or Assign
7
1-50, On
Press Enter to Clr Thermal Register
SP12.4
P
age 12
S
y
s
tem
 S
e
tpoint
s
Lev
el 3
P
a
s
s
w
ord P
rot
ec
ti
on
SP12.2
SP12.3
SP12.1
Setpoint
Page
Security
Level
Description
Factory Setting
Default
Range
Section
Set Date and Time 
(DDMMYY:HHMM)
FACTORY SET; 
##/##/## ##:##
Enter Date (DDMMYYYY)
FACTORY SET;
##/##/####
D=1-31, M=1-12, Y=1970-2069
Enter Time (HH:MM)
FACTORY SET;
##:##
H=00-23, M=0-59
Model #                                              
Firmware REV. #
FACTORY SET;
######            ######
Display Only, Cannot be changed
SP13.2
Press Enter to Access Factory 
Settings
Available to Qualified Factory Personnel
SP13.3
Page 13