PVI Industries PV500-40 User Manual

Page of 6
Page 2 / 6 
 
PV500-40  01/25/11 
1.  DISPLAY AND INTERFACE 
1.1 KEYBOARD 
BUTTONS 
 
SET 
Displays and modifies the temperature set points. 
In programming mode, it selects a parameter or confirms an operation. 
 
UP 
Displays and modifies the energy saving (Night Time setback) settings. 
In programming mode, it browses the parameter codes or increases a 
displayed value. 
 
 
DOWN 
Displays the working hours of the load relays. 
In programming mode, it browses the parameter codes or decreases a 
displayed value. 
 
 
CLOCK 
Changes lower display from Probe 1 (Depending on product, probe 1 may 
display lower tank/inlet or upper tank/outlet temperature or may not be used.) to 
current time and day. 
 
 
EXT 
Changes upper display from Outlet Temperature to Probe 3 (Optional 
Temperature Probe. Used for Outdoor Reset on Boilers) and displays the 
temperature difference of the Inlet Temperature minus Outlet temperature. 
In programming mode it sets the 4-20mA output (password is required). 
 
ON/OFF 
Switches the control ON or OFF. 
1.2 KEY 
COMBINATIONS 
 
 
 
To lock and unlock the keyboard. 
 
 
 
To enter the programming mode. 
 
 
 
To exit the programming mode. 
1.3 
LED ICON LEGEND 
 
LED MODE 
Function 
 
ON 
Temperatures are displayed in Fahrenheit degree 
 
ON 
Temperatures are displayed in Celsius degree 
 
Flashing 
Call for heat time delay 
 
ON 
Call for heat is on 
 
Flashing 
Second stage time delay (On 2-stage units only) 
 
ON 
Second stage on 
 
Flashing 
Freeze protection time delay 
 
ON 
Freeze protection on 
 
ON 
Modulation output signal is in manual control mode  
 
ON 
Modulation output signal is automatically controlled by temperature probe 1 
Ext
 
ON 
The outside temperature is displayed 
 
FLASHING 
Low gas pressure alarm  
 
FLASHING 
High gas pressure alarm  
 
  FLASHING Low-water 
alarm 
 
ON 
Lower LED readout is displaying the clock 
  
FLASHING Alarm 
signal 
 
FLASHING 
Programmed working hours limit is exceeded 
 
ON  
Working hours are displayed in Lower LED readout 
ES 
ON  
The energy saving function is running