2.2 
HOW TO LOCK THE KEYBOARD 
 
 
 
 
1.  Push and hold the UP 
DOWN keys for more than 3 seconds. 
2.  The “POF” message will be displayed and the keyboard is locked. At this point it 
is only possible to view the set point. 
3.  Repeat step 1 to unlock the keyboard. 
 
2.3 
HOT KEY PROGRAMMING (FOR FACTORY SUPPORTED FIELD REPROGRAMMING) 
 
To upload a program from a control to a HOT KEY: 
 
 
To download a program from a HOT KEY to a control: 
 
 
 
 
 
3. ALARMS 
 
Alarm messages are displayed in the upper LED readout and alternate with the default display.  
An alarm LED icon is also illuminated.  
 
Message  Cause 
Results of alarm condition 
“P1” 
Probe 1 failure 
Call for heat and burner second stage 
interrupted; modulation output signal will 
revert to low fire  
“P2” 
Probe 2 failure 
Freeze protection is disabled 
“P3” 
Probe 3 failure 
Outdoor reset disabled 
Warm weather shut down disabled 
“HA” 
High temperature limit set point exceeded 
Buzzer sounds, operation continues 
“LA” 
Low- temperature alarm 
Buzzer sounds, operation continues 
HP 
High gas pressure/low water cut-off alarm 
Unit deenergized after time delay 
LP 
Low gas pressure alarm 
Unit deenergized after time delay 
Mn1 
Maintenance alert for call-for-heat 
Buzzer sounds, operation continues 
Mn2 
Maintenance alert for second stage   
Buzzer sounds, operation continues 
Mn3 
Maintenance alert for freeze protection 
Buzzer sounds, operation continues 
“rtc” 
The real time clock has lost the setting  
Energy saving functions disabled 
“rtF” 
Real time clock failure 
Energy saving functions disabled 
 
  
 
 
   +
   
 
Insert HOT KEY into the TTL connection on the back of the control. 
Press and hold UP + DOWN keys momentarily then press the UP key. 
The “Upl” message will appear while uploading is occurring and the 
“End” message will appear when finished. Push any key to return to 
normal operation. 
 
 
  
 
ON/OFF 
Press the ON/OFF key to turn off the control. Insert the HOT KEY into the TTL connection on 
the back of the control. Press the ON/OFF key again and downloading will begin. The “don” 
message will appear while downloading is occurring and the “End” message will appear 
when finished. Push any key to return to normal operation.