3
 
Hit 
 
SEL
 
 to select Group A. The following menu is displayed:
A. Associate Loads With the Group
Hit 
 
SEL
 
 to select 
 
Associate Loads
 
. The following screen is 
displayed:
There are two ways to choose which loads are associated with the 
group. Hitting 
 
SEL
 
 on the 
 
Select loads for this group 
individually
 
 will present the following screen:
Each load (breaker) will be listed by panel, followed by its current 
membership in this group (
 
YES/NO
 
) and by its description, if one has 
been entered (
 
LIGHTING – R102
 
 in the above example). Use 
 
UP/
DOWN to scroll up and down through the breaker list and SEL to 
change to membership setting to 
YES
 or 
NO
. After all loads have been 
selected for this group, hit BACK twice to return to the 
CONFIGURE 
GROUP A
 screen.
The second option for associating loads is the 
Add all loads
 
method. To use this option, turn ON the primary handle and the con-
trol handle for all loads that will be part of this group. Turn OFF the 
primary handle for all loads that will not be part of this group. Then 
UP/DOWN to move to the 
Add all loads
… option. Hit SEL to 
choose all currently 
ON
 breakers. This may take several minutes while 
all breakers are scanned. After all loads have been selected for this 
group, hit BACK twice to return to the 
CONFIGURE GROUP A
 screen.
  CONFIGURE GROUP A
Group A  GRPA    ON
 OFFICE LIGHTING
Associate Loads______
Associate Inputs
Modify Schedules
Modify Description
ASSOCIATE LOADS
   With Group A
Select loads for this
   group individually
Add all loads which 
   are currently ON
Clear all loads from
   this group
PICK GROUP A LOADS
USE SEL to TGL LOAD
PNL1 Load 16 BK16 YES
 LIGHTING – R101
PNL1 Load 17 BK17 YES
 LIGHTING – R102_____
PNL1 Load 18 BK18 NO
B. Associate Inputs With the Group
If a switch input will be associated with this group, use UP/DOWN to 
highlight the 
Associate Inputs
. Hit SEL to move to the input 
select screen:
Use UP/DOWN to cycle through the available inputs. When the 
correct input is displayed, hit SEL to associate it with the group. 
The input type screen will then be displayed:
The list of input types extends beyond one page. Use UP/DOWN to 
scroll through the choices and highlight the correct switch type. Hit 
SEL to choose it.
Note: Three-way and 3-wire momentary switches require two physi-
cal inputs paired together. Inputs 1 and 2, 3 and 4, 5 and 6, etc., are 
paired together by the system. Selecting either one of them as the 
input will cause the other to be automatically selected for these types 
of switches.
The 
delay time
 screen will be shown next:
To have the load stay on for a certain number of minutes after the 
input has turned off, use UP/DOWN and SEL to pick a number of min-
utes. Otherwise, hit SEL on the 
None
 value. A value other than 15, 30 
or 45 can be entered by choosing the 
enter exact time
 selection.
Hit BACK three times to return to the 
CONFIGURE GROUP A
 screen.
INPUT for GROUP A
  is currently #7
Change input to:
Input  7  DI01  (OFF)
 Maintained +  5 min_
Use up/down to change
Input, SEL to accept
Select the type of
 switch on Input 7
Maintained__________
Maintained(inverted)
Momentary ON / OFF
Maintained Change
Motion Sensor
Photocell 
Select the delay time
 time for Input 7
-15 minutes
None_________________
15 minutes
30 minutes
45 minutes