Moeller Marine XControl PLC System AWB2700-1428GB User Manual

Page of 54
12/01 AWB2700-1428GB
General messages
37
General messages
Deleting programs from the hard disk
Requirement: a bootable version of the program is on the hard 
disk.
X
Use the MSS to choose MAIN MENU r PROGRAM r 
INTERNAL 
r DELETE. 
The name of the program will appear. 
X
Press the MSS.
X
Turn the MSS so that the text ENTER appears instead of menu 
item BACK. 
X
Press the MSS. 
The next higher menu is displayed and the bootable program is 
deleted. There is still, however, an executable version of this 
program in the working memory that is not deleted by this step. If 
the OMS is set to RUN-P, this indicates that the (executable) 
program is still running. The program can only be deleted via a 
Reset (HARD/Original).
Deleting programs from the working memory
The program can be deleted by means of a Reset (HARD/Original), 
following section.
Reset function (initialisation of variables)
The function can be executed via XSoft as well as via the operator 
module. 
Executing Reset via XSoft 
The Reset function can be executed in three different ways via the 
XSoft Online menu or via the operator module of the XC600:
Method 1:
This function initialises the simple variables and POU variables as 
well as those variables that have been declared as PERSISTENT. 
The PLC is switched from RUN to STOP status.
Method 2:
This function initialises the simple variables and POU variables as 
well as those variables that have been declared with RETAIN.
The PLC is switched from RUN to STOP status.
Method 3:
This function initialises the simple variables and POU variables as 
well as those variables that have been declared with RETAIN and 
PERSISTENT.
An XC600 is set to STOP status and the executable program is 
deleted. The bootable program is retained. The PLC can either be 
started by switching on the power supply or via the XC600 func-
tion REBOOT or LOAD. The activated program is started. XSoft also 
offers a program start, however; the program must first be loaded 
from the PC to the XC600.
Executing RESET on the operator module
X
Turn and press the MSS to choose MAIN MENU PROGRAM 
RESET. 
X
Select either WARM, COLD or HARD.
The subsequent NO/YES prompt can also be changed by turning 
the MSS. Pressing the MSS will call up the ENTER? prompt. 
Pressing it once more will execute the Reset.
Executing the MRES function on the OMS 
This function starts a RESET COLD. 
Example: the display shows the basic menu:
X
Switch the OMS from STOP to MRES.
The display will show a solid black rectangle instead of the S:
X
Leave the OMS in the MRES position until an empty rectangle is 
shown. 
PROG: ???
There is no executable program in the PLC.
Attention 
no signal
System error. The power supply in the PLC must be 
switched off and on again.
XSoft
XC600 operator module
Reset
RESET WARM
XSoft
XC600 operator module
Reset (cold)
RESET COLD
XSoft
XC600 operator module
Reset (original)
RESET HARD
17:22:24
S
STOP
PRONAM.PRO
>MAIN MENU
17:22:35
'
STOP
PRONAM.PRO
>MAIN MENU