Moeller Marine XControl PLC System AWB2700-1428GB User Manual

Page of 54
Menu Overview of the Oper-
ator Module
12/01 AWB2700-1428GB
46
HARDWARE
CONFIGURE: After the CONFIGURE menu is called, the display 
shows the current module configuration of the XC600.
AUTOCONFIG:
The functionAUTOCONFIG is always activated. In this state the 
system will scan the module configuration on startup. If the config-
uration does not change, for example, after commissioning has 
been completed, the configuration can be ”frozen” for diagnostic 
tasks.
For this disable the AUTOCONFIG function:
X
Choose MAIN MENU DEVICE HARDWARE 
AUTOCONFIG.
The cursor will be positioned on ON: 
X
Turn the MSS until the display shows OFF.
X
Press the MSS. The word ENTER will appear on the display.
X
Press the MSS to return to the menu.
This function can be re-activated at any time.
The next time that the PLC is started up the PLC will detect if any 
modules are missing or faulty. This is indicated by the SF LED lit.
The following error text will appear in the DIAGNOSTICS ERROR 
menu:
The number 1 in the designation XC-NET-1 indicates the module 
(address):
MAIN MENU: SYSTEM
This menu is used to shut down the operating system or reboot it. 
Turn the MSS to select either SHUTDOWN or REBOOT.
HARDWARE:
 CONFIGURE
 AUTOCONFIG
 BACK
XC-CPU601-4
XC-POW50-XU
XC-NET-DP-M
XC-SYS1
BACK
AUTOCONFIG:
ON
 BACK
Number
(Hardware) address of the module
0
CE000
1
CC000
2
D4000
05.12_15:32
XC-NET-1
NOT DETECTED
BACK