10. Use (2) 5/8” (16mm) screws to secure the wood 
bracket leaving 1/4” (6mm) of each screw exposed for 
hanging the hood. 
Note: 
Dashed line indicates cutout needed for clearance of the 
transition (Figure 9).
Discharge Direction: Horizontal discharge requires a wall 
cutout, as shown in Figure 9, to provide clearance for the 
transition. The location of the cutout is determined by the 
hood installation height.The transition supplied with the 
hood connects to standard 10” (254mm) round duct. 
Figure 11 shows the hood configured for vertical discharge. 
Installations using this method require a cutout in the 
ceiling to accommodate 10" (254mm) duct and the 1/2” 
(13mm) conduit carrying power to the unit. 
Duct covers, sold separately, are available to cover the 
space between the top of the hood and ceiling (see 
Figure 13).
 Figure 8: Transition and Conduit Locations
 Figure 9: Cutout Dimensions
1
1
/
8
(29mm)
3
3
/
16
2
3
/
8
1
7
/
8
7
7
/
8
2
3
/
8
(81mm)
(200mm)
(60mm)
(60mm)
(48mm)
5/8” (.16mm)
DIA clearance
holes for 1/2” 
(12.7mm) conduit to 
Note: 
This figure depicts transition and conduit 
locations only. See Figure 3 & Figure 4 on page 5 
for overall hood dimensions.
junction box
Cooktop
Centerline
Base of
Hood 
Location
23” (584mm)
2
3
/
4
”  (69mm)
12
1
/
2
”  (318mm)
Wall
 Figure 10: Transition Centerline for Horizontal Discharge
 Figure 11: Transition Centerline for Vertical Discharge
10
1
/
4
” (260mm)
10
1
/
2
(267mm) 
Transition
Centerline
Wall
10
1
/
4
(260mm)
18”
(457mm)
5
13
/
16
(148mm)