APC Condenser 2 EC Fan ACCD75208 User Manual

Product codes
ACCD75208
Page of 50
23
InRow RP Technical Data Manual
Chilled Water Data - General
MODEL
ACRP 500 Series
MODULATING VALVES
Size -3 Way Ball Valve - NPT mm (in)
25.4 (1)
AIR SYSTEM - FANS (Standard Filter Installed)
Air Volume - l/s (SCFM)
3162 (6700)
Fan Motor - W (HP)
1100 (1.5)
Number of Fans
3
COOLING COIL - COPPER TUBE/ALUMINUM FIN
Face Area - m
2
 (ft
2
)
0.74 (7.9)
Rows Deep
4
Fins per meter (Fins per inch)
468 (12)
HUMIDIFICATION - SOLID STATE ELECTRODE CANISTER
Flush Cycle
Automatic
Capacity - kg/hr (lbs/hr)
3.0 (6.6)
kW
2.25
REHEAT
Electric - Equally Loaded Three Stage, Finned Tubular, Low-Watt Density
    Capacity - kW (BTU/hr)
9.0 (30,700)
    Stages
3
FILTERS - PLEATED (STANDARD)
Quantity
4
Size - mm (in)
418 x 470 (16.45 x 18.5)
Depth - mm (in)
96 (3.78)
             Efficiency (%)
30
FILTERS - PLEATED (OPTIONAL)
               Quantity
4
               Size - mm (in)
418 x 470 (16.45 x 18.5)
               Depth - mm (in)
96 (3.78)
               Efficiency (%)
85
PHYSICAL DATA
Weight - kg (lbs)
352 (776)
Height - mm (in)
1991 (78.40)
Width - mm (in)
600 (23.62)
Depth - mm (in)
1070 (42.13)
CONNECTION SIZES
Chilled Water
Supply Line - mm (in)
35.0 (1 3/8)
Return Line - mm (in)
35.0 (1 3/8)
Humidifier
Supply Line - mm (in)
6.35 (1/4)
Condensate Drain
Drain Line - mm (in)
12.7 (1/2)
For sustained operation, a maximimum flow rate of 2.2 l/s (34 GPM) is recommended. This may be exceeded by 25% for peak 
conditions.
Maximum working pressure for the unit is 300 psig (2068.4 kPa).
Note: Reduce airflow and cooling capacity specifications by 7% for cooling units run at low input voltage (380 V).